5.7
Positioning the cassette unit
5.7.1
Installation location
Fig.180
1500
1500
1500
Fig.181
1500
1 Indoor unit
2 Lighting
5.7.2
Suspending the unit
7800871 - v01 - 18112021
Select a suitable position in order to achieve a uniform air temperature
in the place of installation.
Adhere to the minimum distances between other objects and obstacles.
Make sure that there is space to install the condensate pipe with a slope
on the chosen location.
1500
MW-6070069-01
50
1
1500
2500
2000
1. Mount the fasteners of the indoor unit in one of the following ways:
MW6020094-01
Caution
Ensure that the installation location is able to take four times the
unit weight and capable of bearing vibration for long periods.
2
3
4000
3 Fan
Important
Ensure that the installation location is able to take four times the
unit weight and capable of bearing vibration for long periods.
Ensure the condensate can properly be drained. Install the unit
slightly sloped towards the drain tap.
with a dowel on which the suspension bolt is screwed.
with a suspension rod fixed directly on the hard structure (steel or
wood).
5 Installation
en
1
MW-6070070-01
159