5 Installation
5.7.3
Installing the condensate pipe
Fig.182
1~1.5 m
Fig.183
160
2. Install a nut to the end and a spring washer to the suspension bolt.
3. Install the indoor unit to the suspension bolt then a washer and a nut
to secure.
4. Adjust the relative position of the suspension hook on the suspension
bolt so that the unit can be in level position in all directions.
5. Tighten the nut and ensure that four hooks are in close contact with
the nuts and washers, to fix the indoor unit.
6. Install the locknut and screw it down to secure the installation.
7. Ensure the unit is secure and does not shake or sway. Ensure that the
center of the indoor unit is aligned with the installation.
MW6020097-01
Caution
The unit includes a condensate pump with a 700 mm lift up
capacity. However after the pump stops, the water still in the pipe
will condensate back and may overflow the drain pan causing a
water leak. To prevent this, ensure there is a downward gradient
of 1/100-150 after the highest point in the pipe.
1. Connect the condensate pipe to the drain tap.
2. Ensure there is a downward gradient of 1/100-150.
3. Insulate the condensate pipe and drain tap (rubber insulation with a
thickness of more than 8 mm) to prevent condensation.
>1/100
MW-6020089-1
4. When draining multiple units into a shared condensate pipe, this
shared pipe should be installed about 100 mm below each unit's drain
tap, as shown in the drawing.
MW-6070068-01