12.1 120 Volt Connections
The XR315 has a total of 8 receptacles. Each receptacle is rated for a maximum load of 15 amps
but the total load of the XR315 must not exceed 15 amps.
12.2 Remote Control Connections
Remote connections are wired to the green 7-pin plug-in Phoenix terminal block on the rear of the
unit next to the power cord. The terminal block itself is provided in the accessory bag that you
will find in the shipping box. After you have made the connections to the terminal block, plug it
into the connector on the rear of the unit. Never solder (tin) wires before inserting in a terminal
block – solder creeps and you will eventually have loose connections!
The connections are shown below:
Pin 1 – Up Input
Pin 2 – Down Input
Pin 3 – Over-Ride Input
Pin 4 – 12 V dc Output
Pin 5 – Common
Pin 6 – Aux Relay Contact
Pin 7 – Aux Relay Contact
12.2.1 Up/Down Control Inputs
The XR315 can be controlled by a DC voltage in the range 5V to 30V, by a contact closure (such
as a relay), or by a switch. In this manual the terms "momentary" and "latching" are used when
describing switches. A momentary switch is considered to be a switch which provides a
connection only while it is actually held pressed, and a latching switch is considered to be a
switch which remains in either the on or the off state (like a light switch). Momentary switches
are preferred for use with the XR315 since multiple control locations can be used, and also
because some of the functions of the XR315 are not available when a latching switch is used (see
programming section). Switches with gold contacts are recommended for the best long-term
reliability. The type of input is selected totally through programming, making the electrical
connections straightforward. The six control options are discussed below:
g) DC Voltage: The XR315 will power up when the voltage is present and power down when
there is no voltage. Connect the positive wire to the "up" input, and the ground (or
negative) wire to "common". Program the input for "5-30 V dc".
h) Contact Closure: The XR315 will power up when the contacts are closed and power down
when the contacts are open. Connect the two wires from the contacts to "up" and
"common". Program the input for "Latching"
© 2024 AMETEK Electronic Systems Protection / Soporte técnico: 1-800-645-9721 / surgex.com
XR315
Manual de usuario
31