18 Specifications
Voltage Rating:
Current Rating:
Power Rating:
Maximum Load Inrush Energy:
Surge Let-through Voltage:
EMI/RFI Filter, Normal Mode:
EMI/RFI Filter, Common Mode:
Voltage Protection Rating (VPR)
Maximum Applied Surge Voltage: 6,000 Volts *
Maximum Applied Surge Current: Unlimited (due to current limiting) *
Maximum Applied Surge Energy:
Number of Outlets:
Remote Control Voltage:
Remote Control Current Draw:
Contact Closure Max. Resistance:
Auxiliary Relay Contact Rating:
12 Volt Output Max. Current:
AC Voltmeter Accuracy:
AC Ammeter Accuracy:
Dimensions (without rack ears):
Weight:
Temperature Range:
Humidity Range:
Agency Listings:
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41
© 2024 AMETEK Electronic Systems Protection / Soporte técnico: 1-800-645-9721 / surgex.com
XR315
120 Volts AC
15 Amps
1,800 Watts
1400 Joules total during power-up
Zero let-through Voltage for a 6000 Volt surge
40 dB @ 100 KHz, 50dB @ 300 KHz, 50 dB @ 3 MHz, 50 dB @ 30
MHz (50 Ohm load)
18dB @ 300 KHz, 30 dB @ 1 MHz, 50 dB @ 5 MHz, 50 dB @ 20 MHz
(50 Ohm load)
330V Line-Neutral
Unlimited (due to current limiting) *
8
5 to 30 Volts DC
3 mA maximum
100 Ohms
30 Volts DC at 1 Amp
40 mA
± 2%
0.1A resolution, ±1A accuracy
17.3" W x 10.5" D x 1.7" H
12 lbs (5.4kg)
5C to 35C
5% to 95% R.H. Non-condensing
Conforms to UL Stds 1283 & 1449, Certified to CSA Std C22.2 No. 8