Aux Output
Aux Delay On
Aux Delay Off
14.5 Front Panel Push Button
The front panel push button allows the unit to be powered up or powered down from the front
panel. There is one menu item associated with the push button which allows it to be disabled or to
operate only after a one second delay. The delay option prevents the unit inadvertently powering
on or off if the push button is accidentally bumped. Note that the push button cannot be used in
conjunction with applied voltage or latching type remote control inputs.
Fr. Panel Button
14.6 Out-of-Range AC Voltage Shut Down
The XR315 has built-in line voltage monitoring and out-of-range shut down. The default limits
are 90V at the low end and 150V at the high end, and shut down begins if the line voltage remains
outside the set limits for 1 second or more. These limits are adjusted by using two menu items,
with the low limit adjustable from 90V to 110V and the high limit adjustable from 130V to 150V.
If the unit has shut down due to an out-of-range line voltage and the line voltage subsequently
returns to normal, power up will only resume if the Power Fail Restore option (section 5.8) has
been set to "Enable".
Low-V Shut Down
High-V Shut Down
14.7 Restore Functions
There are two menu items which, when enabled, allow the XR315 to restore the original "on"
condition after shut-down caused either by loss of AC power (or out-of-range AC) or by an over-
© 2024 AMETEK Electronic Systems Protection / Soporte técnico: 1-800-645-9721 / surgex.com
XR315
When using the aux relay for confirmation select "Confirm". Options
"A", "B" or "C" synchronize the operation of the relay to the same
internal trigger as the receptacles on the rear panel of the XR315.
Choose A, B, or C when the relay is used to control an "RT" type
SurgeX. "Gang" or "Cascade" is selected when two or more XR315s
are ganged or cascaded together. All these options are covered in detail
in the applications section.
Set the delay time in seconds for the auxiliary relay closing. This delay
time begins with the same internal trigger as the receptacles on the rear
panel of the XR315.
Set the delay time in seconds for the auxiliary relay opening. This
delay time begins with the same internal trigger as the receptacles on
the rear panel of the XR315.
Select "Enable" for normal operation, "Delay" to operate only after a
one-second delay, and "Disable" to prevent operation from the front
panel.
Set the low voltage shut down limit from 90V to 110V
Set the high voltage shut down limit from 130V to 150V