first and last units set up as shown, add units in the middle and set them up and connected them in
the same way as the middle unit in the diagram.
The remote control inputs should be connected to the first unit, and the same control options are
available as for a single-unit system. If confirmation feedback is required for a central controller,
use the aux relay contacts on the last unit.
If the low and high voltage shutdown points are narrowed from their defaults of 90V and 150V
this should be done on the first unit only. The other units should be left set to 90V and 150V.The
two restore options should only be enabled (if required) on the first unit.
If an over-ride is required connect it to the last unit and program that unit to accept the type of
over-ride you need.