Check that the two pairs of wires have been correctly
connected and after installation proceed as follows:
1. Disable encoder operation (
2. Set a meaningful open delay (
NOTE: The default settings in the controller satisfy points 1
and 2.
3. Give a START command:
- If both gate panels move, the wires are connected correctly
- If Err7 appears on the display once panel 1 starts to move,
invert the wires connected to terminals K3 (FCA2) and K4
(FCC2)
Err7
- If
appears on the display once panel 2 starts to move,
invert the wires connected to terminals K1 (FCA1) and K2
(FCC1)
GATES WITH SINGLE PANELS
Installation of limit switch
• Connect the open limit switch to terminals K1 (FCA1) and
K5 (COM)
• Connect the close limit switch to terminals K2 (FCC1) and
K5 (COM)
Installation of encoder
• Connect the negative feeds (BLACK cable)
to terminal K5 (COM)
• Connect the positive feeds (RED cable)
to terminal K6 (+)
• Connect the encoder output (BLUE / WHITE) to terminals
K3 (FCA2) and K4 (FCC2)
Check that the two encoder wires have been correctly connected
and after installation proceed as follows:
1. Disable encoder operation (Enco menu)
2. Give a START command:
- If the gate moves, the wires are connected correctly
Err7
- If
appears on the display once the gate starts to
move, invert the wires connected to terminals K3 (FCA2)
and K4 (FCC2)
Enco
menu)
r.AP
menu)
6.11 - EXTERNAL AERIAL
We suggest to use the external aerial (model: ANS433) in order to
guarantee the maximal range.
Connect the antenna hot pole to terminal L1 (ANT) of the control
unit and the braiding to terminal L2 (ANT-).
6.12 - PLUG IN RECEIVER
CITY2+ control unit is suitable for plugging in a MR receiver.
m
WARNING: Pay attention to the way you connect the
removable modules.
MR module receiver is provided with 4 channels and each of them
is suitable for a command of CITY2+ control unit:
g
• CHANNEL 1
START
g
• CHANNEL 2
PEDESTRIAN START
g
• CHANNEL 3
STOP
g
• CHANNEL 4
COURTESY LIGHT
m
WARNING: Before programming 4 channels and
function logics read carefully the instructions of MR.
6.13 - ADI INTERFACE
The ADI (Additional Devices Interface) interface of the control unit
CITY2+ allows the connection to V2 optional modules.
Refer to V2 catalogue or to the technical sheets to see which
optional modules with ADI interface are available for this control
unit.
m
WARNING: Please read the instructions of each single
module to install the optional modules.
For some devices, it is possible to configure the mode for
interfacing with the control unit; in addition, it is necessary to
enable the interface so that the control unit can process the
signals arriving from the ADI device.
i.Adi
Please refer to the
interface and access the device configuration menu.
The ADI device can signal photocell, edge or stop alarms:
• Photocell alarms - the gate stops moving, when the alarm
stops opening restarts.
• Edge alarm - inverts motion of the gate for 3 seconds.
• Stop alarm - the gate stops and cannot restart until the alarm
stops.
- 29 -
programming menu to enable the ADI