8 - QUICK CONFIGURATION
This paragraph concerns a quick procedure to set the control unit
and set it at work immediately.
We recommend following these instructions, in order to
check quickly the correct operation of control unit, motor and
accessories, and then changing the configuration in case of any
non-satisfactory parameter.
1. Call up the default configuration (chapter 8)
m
CAUTION: If there is only one motor, set the open
t.AP2
time,
, to zero in order to inform the controller that
the parameters for motor 2 do not need to be considered.
StoP - Fot1 - Fot2 - CoS1 - CoS2
2. Set items
according to the safety devices installed on the gate.
3. Start the self-learning cycle (chapter 11)
4. check that the automation work properly and if necessary
modify the configuration of the desired parameters.
9 - LOADING OF DEFAULT
PARAMETERS
If necessary, it is possible to restore all the parameters to their
standard or default value (see table at the end)
m
WARNING: This procedure causes the loss of all the
customized parameters, therefore it has been put outside
the configuration menu, to reduce the possibility of
executing it by mistake.
1. Press and hold down the MENU key until the
on the display
2. Release the MENU key: the display will show
MENU key only if you want to leave this menu)
dEF
3. Press the DOWN key:
4. Press the MENU key: no will appear on the display.
Si
5. Press the DOWN key:
will appear on the display.
6. Press the MENU key: All of the parameters are returned to
their default values (see the table on pages 37) and the display
shows the control panel
-dEF
appears
ESC
(press the
will appear on the display.
- 33 -