Switch Bank
4 dip switches (S1, S2, S3, and S5)
control settings for the alarm output.
The fifth dip switch (S4) is used only
to test the delay settings.
When S3 is set to ON, it inverts the
relay function, and the functioning of
S1 and S2.
Failsafe/Alarm Setting
Alarm Mode S3 status
High
ON
Low
OFF
Delay Settings: S1 and S2
High alarm/
S3-ON
overfill protection
Low alarm/dry run
S3-OFF
protection
Sensitivity setting (high or low): S5
S5-ON
High
S5-OFF
Low
Test settings: S4 (inverts the signal).
S4-ON
Enable test
S4-OFF
Normal operation
1.
The manual assumes that the pump should be turned off in the event of a failure. If this is
not the case in your process, make the appropriate connections to suit your application.
A5E32221251
Pointek CLS200/300 (Standard) – QUICK START MANUAL
1 2 3 4 5
ROCKER DOWN
1
: S3
Probe status
covered
uncovered
Effect of S3 position on functioning of S1 and S2
S1-ON
disables delay of alarm de-activation (alarm OFF)
S2-ON
disables delay of alarm activation (alarm ON)
S1-ON
disables delay of alarm activation (alarm ON)
S2-ON
disables delay of alarm de-activation (alarm OFF)
For measuring dry solids or non-conductive liquids.
For measuring conductive liquids, or viscous conductive solids
Check output status and sensor status LEDs to verify delay interval set
by potentiometer P1.
delay: alarm activation
delay: alarm deactivation
failsafe/alarm
test delay settings
sensitivity (High or Low gain)
Dip switches shown in OFF
(open) position.
Alarm status
activated (ON)
activated (ON)
Relay status
de-energized
de-energized
Page EN-13