Installation and connection
5.1
Installation
For dimensions, see Fig. 4-1 on page 8.
– Installation position: horizontal or vertical
– Type 1 / Use in indoor areas
► Fasten the module with 2 M4 screws and a maximum
tightening torque of 2 Nm using the mounting holes
(see Fig. 4-2 on page 8).
Perform the installation only at suitable ambient
conditions (see Ambient conditions on
page 15).
5.2
Electrical connection
Requirements for complying with the protection
classes:
For IP67, all plugs and caps must be properly connected
and the tightening torque of 0.6 Nm must be observed
(see data sheets of connectors and caps).
The external circuits that are to be connected to
this device must be disconnected from the power
supply or dangerous voltage by reinforced or
double insulation and must satisfy the
requirements of the SELV/PELV (Class III) circuit
i.a.w. UL/CSA/IEC 61010-1, 2-201.
Field wiring terminal:
Cable cross-section AWG22 / 0.34 mm
Cable material: Cu
Temperature range of cable: min. 80 °C
CYJV or PVVA UL-approved connectors or
cables must be used.
www.balluff.com
5.2.1
Power supply
Unwanted voltage dips
► Make sure that the power supply of the device is
sufficiently dimensioned to cover start-up and peak
currents and design the fuse protection concept
accordingly.
► The power supply must have a short-circuit fuse.
The total current for the module and sensor supply
must not exceed 4 A.
BNI XG1-505-0A5-K083
M12 A-coded plug (Power IN)
Fig. 5-1:
Top view of M12 plug, A-coded
Pin
Signal
1
L+ (US+)
2
n. c.
3
L– (US–)
4
n. c.
2
Tab. 5-1:
Pin assignment
BNI XG1-505-0A5-K084
M12 L-coded plug (Power IN)
Fig. 5-2:
Top view of M12 plug, L-coded
Pin
Signal
1
L+ (US+)
2
n. c.
3
L– (US–)
4
n. c.
5
FE
Tab. 5-2:
Pin assignment
NOTICE
Description
Module/sensor supply +24 V
Not connected
Electrical ground 0 V
Not connected
Description
Module/sensor supply +24 V
Not connected
Electrical ground 0 V
Not connected
Functional earth