ASSEMBLY
Before assembly, check that the product is complete and has not suffered any damage during
transport.
Close the gas cylinder valve / gas tank valve before assembly!
Inlet manual pump M 14x1 with O-ring
Pressure limiter
Test pressure gauge 0 to 250mbar
(pressure resistant to 2.5bar)
• Connect the hand pump
• Connect the test hose
gasket) by hand tightening.
• Remove the protective cap
• Connect the additional volume
The pipeline of the LPG system is tested at a pressure of 150mbar from the connection to the
pressure regulator up to the closed shut-off devices of the connected appliances. After a
period of 5 minutes for reaching the thermal balance, the pressure is measured for another
5 minutes. For this purpose, set the hand of the pressure gauge to the test pressure.
DISPOSAL
To protect the environment, our products may not be disposed of along with
household waste.
The product must be disposed of via a local collection station or a recycling station.
LIST OF ACCESSORIES
Product name type 150Z
Test hose G 1/4 lh nut x adapter for test point x 750mm
Test pressure gauge 0-250mbar, quality class 1.0
Gasket for pressure gauge
Additional volume vessel 600cm³
Gasket for additional volume
Gasket for outlet connector G 1/4 lh M on leak tester
Set consisting of: Adapter G 1/4 lh F x G 3/8 lh M
and G 1/4 lh F x G 1/2 lh M brass
4 / 12
to the pressure limiter
to the free connection of the test pressure gauge
from the additional volume
to the free connection
Regler- und Armaturen-Gesellschaft mbH & Co. KG
Obernbreiter Straße 2-18 • 97340 Marktbreit / Germany
Tel.: +49 9332 404-0 • Fax: +49 9332 404-43
E-Mail: info@gok.de • www.gok.de • www.gok-blog.de
Dichtprüfgerät Typ 150Z
Outlet test hose G 1/4 lh-M
Additional test volume 7/16-28 UNEF
Protective cap
90° connection with non-return valve
.
.
and start the pumping process.
(
rubber
Order no.
02 618 06
02 616 26
55 211 60
02 611 40
02 611 27
02 600 59
02 617 22
Artikel-Nr. 02 611 51 b