Connections
Case
Assembly
Display
Keypad
Infrared receiver
Clock with backup battery
Buzzer
Clock
Operating temperature
Operating humidity
Storage temperature
Front panel index of protection
Environmental pollution
PTI of insulating materials
Period of stress across the insulating parts long
Category of resistance to fi re
Class of protection against voltage surges category II
Type of action and disconnection
Construction of the control device
Classifi cation according to protection
against electric shock
Device designed to he hand-held or
integrated into equipment designed to
be hand-held
Software class and structure
Cleaning the front panel of the instru-
ment
Serial interface for CAREL network
Programming key
ir33 platform "connections" +030220447 - rel. 2.2 - 15.06.2010
Type of connection
fi xed screw 16A
fi xed screw
estraibili per blocchetti a vite
The correct sizing of the power and connection cables between the instrument and the loads is the responsibility of the installer.
Depending on the model, the maximum current at the common terminals is 12A or 16A. In the max load and max operating temp. conditions,
the cables used must be suitable for operation up to 105°C.
plastic:
E, A dimensions 34.4x76.2x65 mm - mounting depth 56.5 mm
O, L, H dimensions 34,4x76,2x79 mm - mounting depth 70,5 mm
smooth, hard and indeformable panel: side fastening brackets, to be pressed in fully
drilling template: dimensions 28.8 ± 0.2 x 70.8 ± 0.2 mm
digits: 3 digit LED
display: from -99 to 999
operating status: indicated with graphic icons on the display
4 silicone rubber buttons
available depending on the model
available depending on the model
available in all models
error at 25 °C:
error in the temperature range -10T60 °C:
ageing:
discharge time:
recharge time:
IRxxxx(E,A)(P,Q,S,U,V,X,Y,Z)xxx
IRxxxx(E,A,0,L,H)(N,R,C,B,A,M,L,T)xxx
IRxxxx(0,L)(H,I,E,F,G,K,O,W))xxx
<90% RH non-condensing
-20T70 °C
assembly on smooth and indeformable panel with IP65 gasket
2, normal situation
printed circuits 250, plastic and insulating materials 175
category D and category B (UL 94-V0)
1B relay contacts (micro-disconnection)
electronic control device incorporated
class II when appropriately integrated
no
class A
only use neutral detergents and water
External, available in all models
Available in all models
Cross-sections
for cables from 0.5 to 4.2 mm
for cables from 0.5 to 2.5 mm
± 10 ppm (±5.3 min/year)
- 50 ppm (-27min/year)
< ± 5 ppm (±2.7 min/year)
typically 6 months (8 months maximum)
typically 5 hours (< 8 hours maximum)
-10T60 °C
17
Max current.
2
16A
2
12A
Tab. 4.a