MANUAL DE USUARIO - OPTIMA-31 10K / 20K / 30K
08: Bypass mode setting
Interface
09: Maximum battery discharge time setting
Interface
10: Programmable Output (Output 2)
Interface
11: Reserved
Interface
www.xmart-ups.com
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass mode depending on
bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it's not allowed for running in Bypass mode
under any situations.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is acceptable, but manual
bypass is not allowed. Manual bypass means users manually operate UPS for Bypass
mode. For example, pressing OFF button in AC mode to turn into Bypass mode.
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min to 999 min. UPS will shut down
to protect battery if the discharge time arrives before the battery is under voltage. The
default value is 990 min.
DIS: Disable battery discharge protection and backup time will depend on battery
capacity.
Setting (for 10K and 20K only)
Parameter 3:
ON:
Output 2 is set to be power on
OFF: Output 2 is set to be power off. If UPS restarts this setting will go to "ATO"
ATO: Output 2 is configured as programmable output. It will be powered ON until time
or voltage per battery configured in function 11 is reached. Output 2 will power off if low
battery level is reached before time limit.
Setting (for 10K and 20K only)
Parameter 2 = 001: It allows to configure
shutdown time in minutes (from 0 to 300 minutes)
for output 2. When in battery mode, UPS reaches
cut off time, output 2 is powered off.
Parameter 2 = 002: It allows to configure
shutdown battery voltage in Vdc per battery. When
in battery mode, low battery level is reached, UPS
power off output 2.
V. 170502-OPT-31 10K/20K/30K (SPANISH) -
39