Integra Xmart OPTIMA-31 10K Manual De Usuario página 42

Tabla de contenido

Publicidad

MANUAL DE USUARIO - OPTIMA-31 10K / 20K / 30K
12: Neutral loss detection
Interface
13: Battery voltage calibration
Interface
14: Charger voltage adjustment
Interface
15: Inverter voltage adjustment
Interface
www.xmart-ups.com
Setting
Parameter 2:
N.L: Indicates neutral loss detection function.
Parameter 3:
DIS: Disable the neutral loss detection function. The UPS will not detect the neutral loss or not.
ATO: The UPS will automatically detect the neutral is lost or not. If neutral loss is detected, an
alarm will be generated. If the UPS is turned on, it will transfer to battery mode. When neutral is
restored and detected, the alarm will be muted automatically and the UPS will go back to
normal mode automatically.
CHE: The UPS will automatically detect the neutral loss. If neutral loss is detected, an alarm will
be generated. If the UPS is turned on, it will transfer to battery mode. When neutral is restored,
the alarm will NOT be muted automatically and the UPS will NOT go back to normal mode
automatically.
Here, you must mute the alarm and make the UPS go back to normal mode manually. The
operation is: Firstly, enter this menu and press the "Enter" key to make the "CHE" flash.
Secondly, press the "Enter" key again to activate the neutral detection (check). If neutral is
detected, the alarm will be muted and the UPS will go back to normal mode. If neutral is not
detected, the UPS will continue alarming and stay on the latest status until the neutral is
detected well at next manual checking operation. CHE is default setting.
Setting
Parameter 2: Select "Add" or "Sub" function to adjust battery voltage to real figure.
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
Setting
Parameter 2: you may choose Add or Sub to adjust charger voltage
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all batteries first to get the
accurate charger voltage.
* Any modification should be suitable to battery specifications.
Setting
Parameter 2: you may choose Add or Sub to adjust inverter A voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the default value is 0V.
V. 170502-OPT-31 10K/20K/30K (SPANISH) -
40

Publicidad

Tabla de contenido
loading

Tabla de contenido