Codigos De Alarma En Lcd; Eliminacion De Alarmas - Integra Xmart OPTIMA-31 10K Manual De Usuario

Tabla de contenido

Publicidad

MANUAL DE USUARIO - OPTIMA-31 10K / 20K / 30K

CODIGOS DE ALARMA EN LCD

WARNING
WARNING
CODE
DESCRIPTION
01
Battery unconnected
02
Input Neutral loss
04
Input Phase Abnormal
05
Bypass Phase Abnormal
07
Battery over charge
08
Low battery
09
Overload
0A
Fan failure
0B
EPO enable
0D
Over temperature
0E
Charger failure
10
L1 Input fuse broken
21
In parallel systems: line situation different
22
In parallel systems: bypass situation different
33
Locked in bypass after overload 3 times in 30min
34
Converter current unbalance
35
Battery fuse broken
36
Inverter inter-current unbalance
3A
Cover of maintain switch is open
3C
Utility extremely unbalanced
3D
BYPASS unstable
ADVERTENCIA:

ELIMINACION DE ALARMAS:

** Algunas alarmas pueden bloquear el UPS evitando su operación normal incluso una vez que la falla original que causó la alarma ha
sido resuelta. El técnico debe asegurarse que la falla original ha sido resuelta para posteriormente eliminar la condición de alarma
mediante la selección simultanea de los pulsadores
estado de BYPASS (conectado a la fuente AC pero sin haber sido encendido mediante el pulsador de ON.
www.xmart-ups.com
UP
y
DOWN
en el panel frontal del equipo mientras el UPS se encuentra en
V. 170502-OPT-31 10K/20K/30K (SPANISH) -
43