CARLO GAVAZZI WM20 Manual De Instrucciones página 41

Ocultar thumbs Ver también para WM20:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Measurement
Problem
Cause
The settings of CT and/or VT
are not correct and therefore the
measurement exceeds the maximum
admissible value, or is the result
of calculations with at least one
measurement in the status EEEE
The text 'EEEE'
The analyzer is not used within the
appears in
expected range and therefore the
place of a
measurement exceeds the maximum
measurement
admissible value, or is the result
of calculations with at least one
measurement in the status EEEE
The analyzer has just been switched
on and the set interval for calculating
the average power values (default:
15 min) has not yet elapsed
'Err' appears
The value entered is out of range
while the
parameter is
being set
Possible solution
Modify the parameters CT
and VT
Uninstall the analyzer
Wait. To modify the interval,
go to the page Dmd in the
settings menu, see "Settings
menu" on page 24
Check the range of
admissible values on the
relative page displayed or
see "Settings menu" on page
24 and re-enter the value.
8021572 | WM20 | © 2016 | CARLO GAVAZZI Controls SpA
41

Publicidad

Tabla de contenido
loading

Tabla de contenido