Configuration mode
M C BAC MS module
RS485 port
Protocol
Communication type
Connection type
Supported services
Supported objects
Configuration parameters
Configuration mode
Ethernet port
Protocols
Client connections
Connection type
Configuration parameters
Configuration mode
Via keypad or UCS software
BACnet MS/TP (measurement reading and object
description writing)
Multidrop, one-way
2 wires, maximum distance 1000 m
"I-have", "I-am", "Who-has", "Who-is", "Read-property
(multiple)"
Type 2 (analogue value including COV property), type
5 (binary value, for alarm transmission), type 8 (device)
Settings menu, sub-menu BACnet, see "Settings
menu" on page 24
Via keypad or UCS software
Modbus TCP/IP (configuration)
Maximum 5 simultaneously
RJ45 connector (10 Base-T, 100 Base-TX), maximum
distance 100 m
Settings menu, sub-menu Ethernet, see "Settings
menu" on page 24
Via keypad or UCS software