TECHNICAL FEATURES
Microprocessored Module compatible with Notifier protocol, MMT is designed to manage a single detector. For correct
module working it is necessary 24Vdc regulated source power (it is possible to feed module from panel or from an external
power supply). The module is also provided of power output for gas detector on block connector. The internal power supply
is optoisolated from communication line.
ELECTICAL FEATURES
LED output: suited for INDICATOR.
4÷20mA input: PTC protected input voltage of
30 Vdc, impedance input 155ohm to ground.
Loop voltage input: 15÷32 Vcc.
Stand-by loop:
24Vdc, answer each 5 sec. and LED on: 350μA Typical
growth (resp. 0,2Hz) LED on 70μA
Typical growth (resp. 0,2Hz) without protection 30μA.
External power input: 15÷30Vdc max (optoisolated from
loop).
Current fromm external power supply: 10mA max
(module) + current necessary to feed GAS detector
Gas detector power output: prtected by 400mA
automatic fuse protection
Maximum current output: 300mA.
NOTE 1 - In supervision mode the module checks the power supply voltage beetwen 3 – 4 terminals.
When the tension is lower then 4 Volt the module reports a falut signal to the control panel.
ADDRESS CONFIGURATION
Each module use one of 99 available address for detectors
on loop. The module addressing is achieved through decimal
rotative switches (1-99)
LEDS VISUALIZATIONS MEANING
UNITS
(B)
GREEN
YELLOW
Blink
OFF
Blink
OFF
OFF
OFF
OFF
OFF
Blink
OFF
NOTIFIER ITALIA S.r.l.
MILANO - ITALY
TENS
(A)
GREEN
RED
With Blink function enabled in panel
Blink
A side regular B side regular
OFF
A side in short circuit B side regular
Blink
A side regular B side in short circuit
OFF
Módulo no alimentado.
Isolator circuit excluded by DIP switch
ON
With input in alarm
Tel. +39 – 02 – 51 897.1
Fax. +39 – 02 – 51 897.30
Temperature: 0°C  + 50°C.
Humidity: 10  93% (no condensing).
Weight: 58 grams.
ISOLATOR
Max short circuit current on the loop: Ismax: 1A
Maximum isolator leakage current in presence
of short circuit: Ilmax: 12mA
Max impedance aditted without short circuit on the
loop Zc max: 0,135Ω
On voltage: 6V
Recovery voltage: 7V
Response time: 300µs
Recovery time:150µs
TERMINAL BLOCKS
-
1
LOOP (
) IN
2
LOOP (+) IN
-
3
Detector
4
Signals 4÷20mA
5
Detector +
-
6
Power Ext
7
Power Ext +
8
Output Ext. LED 1
-
9
LOOP (
) OUT
10
LOOP (+) OUT
Units
S-589.1-MMT-ENG rev.A.2
DIPSWITCH
CONFIGURATIONS
SW
Built in ISOLATOR
1
2
module
and
ON
EXCLUDED
OFF
INCLUDED
Ten
s
4 / 4