13 - OPERATION DEFECTS

This paragraph shows some possible operation defects, along with
their cause and applicable remedy.
MAINS led does not switch on
It means that there is no voltage on CITY2+ control unit card.
1. Before acting on the control unit, disconnect through the
disconnecting switch on the power line and remove the power
supply terminal.
2. Be sure that there is no voltage break upstream the control
unit.
3. Check whether the fuse is burnt-out, if so replace it with same
value.
OVERLOAD led is on
It means that there is an overload on accessory power supply.
1. Remove the extractable part containing terminals K1 to K10.
OVERLOAD led will switch off.
2. Remove the overload cause.
3. Reinsert the terminal board extractable part and check that this
led is not on again.
Too long pre-blinking
When a Start command is given and the blinker switches on
immediately but the gate is late in opening, it means that the
setup cycle count down expired and the control unit shows that
service is required.
DESCRIPTION
Anti-skid
When an opening or closing operation is interrupted by a command or
for the intervention of the photocell, the set-up time for the opposite
movement would be excessive, so the control unit operates the motors
only for the time necessary to recover the actually covered journey.
This could be not sufficient, particularly in the case of very heavy gates,
as because of the inertia at the inversion moment the gate runs an extra
space in the previous direction that the control unit is not able to take
into account. If after an inversion the gate does not return exactly to the
starting position, it is possible to set an anti-skid time that is added to the
time calculated by the control unit in order to recover the inertia.
Function disabled
Anti-skid time
End of Programming
This menu allows to finish the programming (both default and
personalized) saving the modified data into memory
It does not exit from the program menu
It exits from the program menu by storing the setup parameters
Error 0
When a start command is given, the gate does not open and the
display shows the message
This means that the buffer batteries do not have sufficient power
to open the gate. It is necessary to wait for the return of mains
power, or to replace the drained batteries with new ones.
Error 1
The following writing appears on display when you exit from
Err1
programming
It means that changed data could not be stored.
This kind of defect has no remedy and the control unit must be
sent to V2 S.p.A. for repair.
Error 2
When a Start command is given and the gate does not open and
Err2
the display shows
It means that MOSFET test failed.
This kind of defect has no remedy and the control unit must be
sent to V2 S.p.A. for repair.