If the room temperature is lower than the required value, it is advisable to set a higher order curve and vice versa. Pro-
ceed by increasing or decreasing in steps of one and check the result in the room.
This parameter is used only if time programming has been activated. See *** 'Time programming' on page 198
A
***
Outside Temperature Heating OFF
Access the "Out Temp Heat Off" to activate the function: between 7°C and 30°C.
If activated, this function will deactivate the heating demand whenever the temperature measured by the external probe
is higher than the programmed value.
The heating demand will be reactivated as soon as the temperature measured by the external probe is lower than the
programmed value.
Adjustments from remote timer control
If the Remote Timer Control (optional) is connected to the boiler, the above adjustments are managed accor-
A
ding to that given in table 1.
Table. 1
Heating temperature adjustment
DHW temperature adjustment (with
optional hot water tank installed)
Summer/Winter Switchover
Eco/Comfort selection (with optional hot
water tank installed)
Sliding Temperature
EN
90
85
80
70
60
50
40
30
20
20
10
fig. 28 - Compensation curves
90
10
9
8
85
80
70
60
50
40
30
20
fig. 29 - Example of parallel offset of compensation curves
The adjustment can be made from the Remote Timer Control menu and the boiler control panel.
The adjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer mode has priority over a possible Remote Timer Control heating demand.
On disabling DHW from the Remote Timer Control menu, the boiler will select the Economy
mode. In this condition, the button detail 10 - fig. 1 on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the boiler will select the Comfort
mode. In this condition, with the button detail 10 - fig. 1 on the boiler panel it is possible to select
one of two modes.
Both the Remote Timer Control and the boiler card manage Sliding Temperature adjustment:
Sliding Temperature overrides the boiler card.
cod. 3541Q760 - Rev. 00 - 02/2019
10
9
8
7
6
5
4
3
2
1
0
-10
-20
90
6
5
9
8
7
10
7
85
6
80
5
70
4
60
3
50
2
40
1
30
20
4
3
2
1
203

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Force w 80Force w 99Force w 120Force w 150Force w

Tabla de contenido