Legend
72a
1st zone (mixed) room thermostat
72b
2nd zone (mixed) room thermostat
72c
3rd zone (direct) room thermostat
130
Hot water tank circulating pump
138
External probe
139a
1st zone (mixed) Remote Timer Control
139b
2nd zone (mixed) Remote Timer Control
139c
3rd zone (direct) Remote Timer Control
155
Hot water tank probe
300
Legionella protection circulating pump
315a
1st zone (mixed) mixing valve
A = OPENING PHASE
B = NEUTRAL
C = CLOSING PHASE
315b
2nd zone (mixed) mixing valve
A = OPENING PHASE
B = NEUTRAL
C = CLOSING PHASE
I*
ISPESL safety devices (when required - not supplied)
To manage the sliding temperature it is necessary to purchase the external probe accessory code 013018X0
If a hot water tank probe (not supplied) is used, it is necessary to purchase the NTC probe accessory code 1KWMA11W (2 mt.)
or code 043005X0 (5 mt.)
If a hot water tank thermostat (not supplied) is used, it is necessary to purchase the accessory kit code 013017X0 (to be connec-
ted in place of the Hot Water Tank Probe)
- Parameters
Each system requires a different parameterization. Follow the access procedure given below.
"Configuration - Parameters Menu"
Check/Change parameter b02 of the "Configuration - Parameters Menu" to 9.
Check/Change parameter b08 of the "Configuration - Parameters Menu" to 1.
Check/Change parameter b04, b05 and b06 of the "Configuration - Parameters Menu" according to the values given
in the table *** 'Configuration - Parameters Menu' on page 227 ***.
- Parameters FZ4B
See relevant manual in Kit.
218
317a
1st zone (mixed) safety thermostat
317b
2nd zone (mixed) safety thermostat
318a
1st zone (mixed) circulating pump
318b
2nd zone (mixed) circulating pump
318c
3rd zone (direct) circulating pump
319a
1st zone (mixed) delivery sensor
319b
2nd zone (mixed) delivery sensor
M
Delivery
R
Return
a
1st zone (mixed)
b
2nd zone (mixed)
c
3rd zone (direct)
d
Hot water tank circuit