Pre-heating enabled
Preheating heat request
External probe presence
Domestic water heat request
Heating heat request
Antifreeze heat request
Flame present
To restore the functioning after the appearance of a fault code of
the boiler press for a second the button BACK/RESET .
If the reset attempts do not reactivate the boiler, request the intervent
of the Technical Assistance Centre.
The A99 fault code means that you have exceeded the maximum
number of reset possible by remote control BeSMART.
In this case, the operations of RESET must be carried out ONLY from
the panel of the boiler as indicated below:
- set the mode selector to
return it to the desired position
Fault A04
Check the pressure value indicated by the manometer, if less than
0.3 bar position the function selector to
to fill the boiler until the pressure reaches a value of between 1 and
1.5 bar. Then press the BACK/RESET
If pressure drops are frequent, request the intervention of the
Technical Assistance Centre.
Fault A06
The boiler functions normally but does not guarantee a constant
domestic hot water temperature, which remains set at around 50°C.
Contact the Technical Assistance Centre.
Fault A07 - A08
Contact the Technical Assistance Centre.
Fault A09
The boiler is equipped with an auto-diagnostic system which, based
on the total number of hours in certain operating conditions, can
signal the need to clean the primary exchanger (alarm code 09 with
flue gases probe counter >2.500).
Once the cleaning operation has been completed, reset to zero the
total hour meter with special kit supplied as an accessory following
procedure indicated below:
- disconnect the electrical supply;
- remove the shell and turn the instrument panel;
- remove the electrical parts inspection cover, undoing the 2 fixing
screws;
- as you electrically power the boiler press the CO button for at least
4 seconds to check that the counter resets. Remove and restore
power to the boiler; on the display the counter is shown after the
"-C-" indication.
b
Live electrical parts.
NOTE
The meter resetting procedure should be carried out after each in-
depth cleaning of the primary exchanger or if this latter is replaced.
To check the status of the totalled hours multiply the value shown by
100 (ex: shown value of 18 = totalled hours 1.800 – shown value of 1
= totalled hours 100). The boiler continues to operate normally even
with the alarm active.
4.5
Boiler configuration
On the electronic card there is a series of jumpers (JPX) which
allow the boiler to be configured; access is possible by removing the
electrical parts inspection cover after setting the main switch to off.
To access the card operate as follows:
- set the system's main switch to off
- undo the shell fixing screws, then move the shell base forward and
then upwards to unhook it from the chassis
- lift and then turn the instrument panel upside down
- remove the electrical parts inspection cover, undoing the 2 fixing
screws to access the jumpers (fig. 38).
(OFF), wait 5-6 seconds and then
(summer) or
(winter).
(OFF) and turn the tap
button.
P
P flashing
60°C
80°C
JUMPER JP7 - fig. 39
pre-selection of the most appropriate boiler heating temperature
adjustment field depending on the type of system.
Jumper not on - standard system
Standard system 40-80 °C.
Jumper on - floor system
Floor system 20-45 °C.
From the factory the boiler is configured for standard systems.
JP1
Enabling front knobs for calibration
JP2
Heating timer reset
JP3
Calibration (see "Adjustments" section)
JP4
Absolute domestic hot water thermostat selector
JP5
do not use
Enable night-time compensation function and pump in
JP6
continuous mode (only with external probe connected)
Enable standard/low temperature systems
JP7
management (see above)
JP8
Do not use
4.6
Setting the thermoregulation
Thermoregulation works only with the external probe connected,
therefore, once installed, connect the external probe to the specific
connection provided on the boiler terminal board.
This enables the THERMOREGULATION function.
Choice of the compensation curve
the display shows the value of the KT curves multiplied by 10
(example 3.0 = 30)
THERMOREGULATION CURVES
CURVE DI TERMOREGOLAZIONE
100
90
T80
80
70
60
50
T45
40
30
20
20
15
10
Temperatura esterna (˚C)
Outside temperature [°C]
T80 - maximum std system heating set point temperature
(JP7 not on)
T45 - maximum floor system heating set point temperature
(JP7 on)
MySMART C.S.I.
Signal
Signal
Signal
Signal
Signal
Signal
Signal
3,0
2,5
5
0
-5
-10
2,0
1,5
1,0
0,8
0,6
0,4
0,2
-15
-20
11