Assembly On Yardy-Ev - Yardy-I - Yardy Id - RHOSS KCMS/PCM Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

BrioEV – Brio-I version MVP - MVT
Probe ST1 must be mounted in the rel ati ve housing at the side of the
unit (ref. 1 in the figure below) and the Probe Out function must be set
on the c ontrol panel (s ee paragraph I.2.1.7).
1
BrioEV – Brio-I version MOP – MOT – IVP – IVF – IOP
Use the wall-mounted control panel to detect the room temperature
(KPCM accessor y), by setting the Probe In function (see paragraph
I.2.1.7). In this cas e, the cable of probe ST1 c an be wound and left
inside the board c ontainer. If the control panel is positi oned in an area
where the c orrect room temperatur e cannot be read, probe ST1 mus t
be mounted i n a positi on i n which the bulb is in contact with the air in
the room; set the Probe Out functi on on the control panel (see
paragraph I.2.1.7).
Probe ST2 must be passed through one of the holes on the bac k panel
of the unit. It mus t then be fas tened to an elbow of the exc hanger with
the clip supplied in the kit (ref. 1 in the figure below).
1
II.3.2
ASSEMBLY ON YARDY-EV - YARDY-I -
YARDY ID
Open the doors and us e a screwdri ver to remove the screws with which
the c abinet is s ecured to the body of the unit (figure below).
1
ST2
Open the c over of the board contai ner (ref. 1 in the figure below).
Secure it to the opposite side of the water connecti ons using the screws
supplied with the kit (see the figure bel ow). F asten the s upport of the
control panel (not pr esent in the KCMS and KCMI Kits, ref. 2 in the
figure below) to the upper end of the bac k panel using the screws
supplied with the kit (see the figure bel ow).
Attac h the adhesi ve l abel (ref. 6 in the previous figure) to the bac k panel
of the unit i n line with the fastening holes of the ter minal board. Then
fasten the termi nal board (ref. 3 in the previous figure) usi ng the screws
supplied with the kit. Attac h c onnectors 4 and 5 (s ee the previous
figure) and c onnect the earth to the screw on the bac k panel (see the
figure below) and then cl ose the cover of the board c ontainer.
Yard yEV – Yard y-I ver sion MVP - MVT
Probe ST1 must be mounted with the rel ati ve s pring supplied with the
kit (see the figure bel ow). The Probe Out func tion must be s et on the
control panel (see paragraph I.2.1.7).
36
SECTION II: INST ALL ATION
2
ST2
1
6
ST1
3
4
5
KCMI
1
6
ST1
3

Publicidad

Tabla de contenido
loading

Productos relacionados para RHOSS KCMS/PCM

Este manual también es adecuado para:

KcmsKcmiKpcmKtcmKicm

Tabla de contenido