Technical Data - Eaton CROUSE-HINDS Serie Instrucciones De Uso

Aparatos para iluminación de depósitos en atmósferas explosivas
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1. Safety Instructions
This product should be Installed and connected by skilled electricians
and instructed personnel in accordance with IEC/EN 60079-14 and the
respective national legislation on electrical equipment for explosive
atmospheres.
The national safety rules and regulations for the prevention of acci-
dents, as well as the safety instructions, like this text set in bold-ita-
lics in these operating instructions manual, shall be observed.
The luminaries must not be operated in Zone 0 or 20 hazardous areas.
The requirements of IEC/EN 60079-31 regarding excessive dust depo-
sits and temperature must be considered by the user. The indicated
surface temperatures are not related to a layer above 5mm thickness.
Before opening, electrical power to the luminaire must be turn off du-
ring at least 10 minutes!, To allow adequate cooling.
The temperature class and explosion group stated on the luminaire
and in table 2, shall be observed. To ensure adherence to the tem-
perature class or surface temperature stated on the type label of the
luminaire, and in table 2, the permissible ambient temperature shall
be observed.
Light fi tting shall be used for their intended purpose and shall be un-
damaged and in a perfect and clean conditions.
Keep tightly closed when in operation.
The technical data indicated in point 3 as well as those indicated in
light fi tting, must be observed.
Modifi cations or design changes to this luminaries that can affect the
explosion protection are not permitted.
Avoid multiple, short time switching operation.
Only original EATON Crouse-Hinds Series spare parts may be used as
replacements and for repairs.
Repairs that affect the explosion protection may only be carried out
by EATON Crouse-Hinds Division or by a qualifi ed electrician in com-
pliance with the respective national regulations.
Prior to being put into operation, the luminaries shall be checked in
accordance with the instructions as per section 6.
Before initial operation, any foreign matter shall be removed from
light fi tting, do not keep this operating instructions manual inside of
the luminaire during its operation.
2. Conformity with standards
This equipment is conform to the standards specifi ed in the EU-Declaration
of conformity. It has been designed, manufactured and tested according to
the state of the art and according to EN ISO 9001 and IEC 80079-34.

3. Technical data

Marking:
Temperature class and max. surface
temperature:
Light fi tings with indirect entry Ex d e have a separate conexion box in "e" increase
safety mode.
EC-type examination certifi cate:
Rated voltage:
Terminals:
Degree of protection
IEC/EN 60529:
Insulation class IEC/EN 60598:
Perm. ambient temperature:
Low temperature version:
Tw for lamps must be obeserved, if the lamp is not included, EATON cannot guaran-
tee its lifetime.
Storage temperature in original
packaging:
Enclosure material:
Glass material:
Enclosure surface fi nish:
Color of enclosure
(standard version):
Dimensions:
Cable entries:
II 2 G Ex d e IIC T6...T3 Gb
II 2 D Ex tb IIIC T85ºC...T140°C Db
See table 2
LOM 02ATEX2035
See table 1 and label of the luminaire
2x2,5mm
2
L,N,PE int.: 2x6mm
2
(use ring lug, not included)
IP 66
I
-20ºC to + 55ºC
-50ºC to + 55ºC
-50ºC to + 55ºC
Aluminium alloy casting (Cu free)
Borosilicate glass
Plastic powder coating
RAL 7032, cover RAL 7016
See Fig. 1
2xM25x1,5 one with blanking plug
4. Field of application
These accessories are intended for use in potentially explosive atmosphe-
res in Zones 1, 2 in accordance with IEC/EN 60079-10-1 and in Zones
21,22 in acordance with IEC/EN 60079-10-2. The enclosure materials
used, including any external metal parts, are high quality materials that en-
sure a corrosion resistance and resistance to chemical substances accor-
ding to the requirements for use in a "normal industrial atmosphere", como
ejemplo entre otros, los siguientes:
- Copper free aluminium alloy casting
- Plastic powder coating fi nish
- Stainless steel
- Borosilicate glass
In case of use in an extremely aggressive atmosphere, please consult to
the manufacturer.
5. Use/Properties
This light fi tting can be use inside or outside to illuminate areas with poten-
tially explosive atmospheres. The temperature class, explosion group and
permissible ambient temperature can be found in the tables and technical
data of this instruction manual.
The data according to sections 2 and 4 shall be taken into account during
use. Applications other than those described are not permissible without a
written declaration of consent from EATON Crouse-Hinds Division.
During operation the instructions stated in section 7 of the operating instruc-
tions shall be observed. The sole responsibility with respect to the suitability
and proper use of these luminaries lies with the operator.
6. Installation
The IEC/EN 60079-14, relevant national regulations and the generally re-
cognized rules of engineering shall be applied for the installation and ope-
ration.
Transport and storage of the luminaries is permitted in the original packa-
ging and specifi ed positions only.
Pay attention when installing, maintaining or repairing the light fi t-
tings, do not damage the fi re-fi nish of the glass surface by abra-
sions, sanding, small strokes, etc. that can weaken their mechanical
functions.
Intensive sun radiation in areas of high ambient temperatures may
cause inadmissible temperature rise inside of the luminaries. This
may result a decrease in lifetime of the electronic components inside
of the luminaries. Therefore those luminaries should be switched off
during daytime by a photocell control.
The improper installation and operation of light fi ttings can result in
the invalidation of the guarantee.
6.1 Mounting
Luminaries are suitable to mounting with straight or asymmetric legs, the
accessories are not included, see EATON Crouse-Hinds Series catalogue
for the correct selection of the mounting accessories.
The light fi tting may only lie fl at on and be fi xed torsion-free to the fastening
points provided for direct assembly. The screws chosen shall fi t the fi xing
hole and shall not damage the hole (e.g. use of a washer, select the correct
length, etc.). The number of screws used for fi xing the equipment shall
correspond to the number of fi xing holes in the light fi tting.
Special attention shall be paid to the PE connections.
Warning: Over tightening might damage the light fi tting.
PE ext.
6.2 Opening the device / Electrical connection
Before opening the light fi tting, it is necessary to ensure that there is
no voltage and it must be allowed to cool down for 10 minutes after
switching off, as general precaution.
The connection of explosion-protected light fi ttings may only be carried out
by specialists. Luminaires with indirect entries shall use Exe cable entries,
whereby the mounting instructions for the cable entry shall be taken into
account (see Section 6.3 Cable Entries).
Ex-de, luminaries with indirect cable entries, have a separate conne-
xion box in "e" increase safety mode of protection.
Warning: In order to establish the mode of protection it is essential
to pay attention to the correct mounting of the cable and cable entry.
5/12

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Kfl serieKfl 50 imKfl 7 ledKfl 50 timCrouse-hinds kfl serie

Tabla de contenido