EGL-M6 grounding indicator with automatic
pump control and ground verification system
Installation & maintenance information
APPLICATION
EGL grounding indicators are to be permanently mounted in a secure location adjacent to
loading/unloading area. EGL grounding indicators are connected to tank vehicles, drums or
other containers before beginning transfer of combustible materials. While connected, the
EGL grounds static electricity and continuously verifies the presence of a static grounding
system. The EGL can be installed to actuate remote devices (lights, horns) to announce
that a safe static ground has been established, or to send an alarm when the ground is
interrupted. An EGL grounding indicator is recommended to be used in the control circuit
of a pump to prevent it from being started until the static grounding circuit is completed,
and to shut down the pump automatically if the static grounding circuit is disconnected.
INSTALLATION
To provide protection against fire or shock hazard, the electrical power must be
OFF before and during installation and maintenance.
To ensure proper operation of the EGL210, two (2) separate ground leads from the
electrical supply panel must be provided: one to terminal #3 and the other to the
green ground lug on the enclosure interior. This provides a continuity check to verify
the EGL210 is grounded.
WEIGHT = 32 lbs (14.5 kg)
IF 1879 • 03/19
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
! WARNING
! CAUTION
1" NPT CONDUIT ENTRY
WITH 3/4" NPT REDUCER
DIMENSIONS - INCHES [MILLIMETERS]
Copyright © 2019, Eaton's Crouse-Hinds Division
EGL grounding indicators are suitable for use in Class I, Groups B, C, D; Class II, Groups
F , G, and Class III hazardous (classified) areas as defined by the National Electrical Code
(NEC).
EGL grounding indicators should be installed, inspected and serviced by qualified and
competent personnel.
Read all instructions before starting installation of this product.
Contact your Eaton's Crouse-Hinds Division sales representative, Customer Service or
your Crouse-Hinds distributor if you have any questions.
1.
Select a mounting location that will provide suitable strength and rigidity for
supporting the enclosure, all contained wiring and control devices. Figure 1 shows
mounting dimensions.
•
Hazardous location information specifying Class and Group listing is marked
on the enclosure nameplate.
•
Conduit sealing fittings must be installed in accordance with Section 501
of the National Electrical Code. An appropriate seal shall be installed within
18" (45.7 cm) of the enclosure for Groups B.
•
All unused conduit openings must be plugged. Plug must engage a minimum
of five (5) full threads and be a minimum of 1/8" (.318 cm) thick.
279.4
11.00
C L
76.2
3.00
44.6
1.75
FIGURE 1
! CAUTION
3/8" [9.5] DIAMETER BOLT
325.1
12.80
216.2
8.51
159.9
6.30
IF 1879
282.6
11.13
127
5.00