Hazard•Gard® XPL Class I, Division 1
Linear LED
Installation & Maintenance Information
APPLICATION
Linear LED fixtures are suitable for use in the following hazardous (classified)
locations as defined by the National Electrical Code (NEC
The assembled luminaire shall be installed in accordance with the National
Electric Code NFPA70, and American Bureau of Shipping and Coast Guard CG-
259 requirements.
NEC/CEC
•
Class I, Division 1, Groups C, D
•
Class I, Zone 1, Group IIB
•
Class II, Division 1, Groups E, F , G
•
Class III
•
Wet location, IP66, Type 4X
These luminaire housings shall be used with UL Listed Eaton's Crouse-Hinds
Series hazardous locations luminaire fitting mounting means, Cat. Nos. PM Kit
1.25, PM Kit 1.5, PM Kit 2.0, ZP1050MTK, ZP1057MTK, PM Kit 1.25P , PM Kit
1.5P , PM Kit 2.0P , ZP1050MTKP , ZP1057MTKP .
!
To avoid the risk of fire, explosion or electric shock, this product should
be installed, inspected and maintained by a qualified electrician only, in
accordance with all applicable electrical codes.
!
To avoid electric shock, be certain electrical power is OFF before and during
installation and maintenance. Fixture must be supplied by a wiring system
suitable for Class I, Division 1 per NEC with an equipment grounding
conductor. To avoid burning hands, make sure luminaire is cool when
performing maintenance.
!
To avoid explosion, make sure the supply voltage is the same as the fixture
voltage.
Do not install where the marked operating temperatures exceed the ignition
temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on the
fixture nameplate.
Use only replacement parts from Eaton's Crouse-Hinds.
Use proper supply wiring as specified on the fixture nameplate.
All gasket seals must be clean and undamaged.
Before opening, electrical power to the fixture must be turned off. Keep
tightly closed when in operation.
!
To avoid explosion, seal luminaire conduit within the distance given in
Table 1, and in accordance with local electrical code requirements and NEC
Article 501 (CEC Section 18).
Model
S917 (Low Temperature Operation)
All other models
IF 1790 • 12/15
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
):
®
WARNING
WARNING
WARNING
WARNING
Groups C & D
6 inches (152mm)
18 inches (457mm)
Table 1
Copyright © 2015, Eaton's Crouse-Hinds Division
UL Standards:
•
UL844 Hazardous (Classified)
•
UL1598 Luminaires, UL1598A Marine
•
UL8750
CSA Standard:
•
CSA C22.2 No. 250
•
CSA C22.2 No. 137
Refer to the fixture nameplate for specific classification information, maximum
ambient temperature suitability and corresponding operating temperature
(T-number).
Linear LED fixture construction is designed for use indoors and outdoors in
marine and wet locations, where moisture, dirt, corrosion, vibration and rough
usage may be present.
INPUT VOLTAGE:
•
UNV1: 100-277 VAC 50/60 Hz and 108-250 VDC
•
UNV34: 347-480 VAC 50/60 Hz
STORAGE ENVIRONMENT:
The XPL Luminaire and accessories must be stored in an ambient from -40°C
to +85°C.
IF 1790
Page 1