Installation
Dip Switch Configuration
X7
4
3
2
1
14 | SCA06
Table 3.1: Dry Contact / OSSD selector
Both switches set to Dry Contact. This configuration must
be chosen when the safety signals are commanded by dry
contacts, for example, relay contacts, as shown on
on page 16
One switch set to "D" (Dry contact) and another set to "O"
(OSSD). This is a not valid combination and results on a Fault
state (F0160) shown by the servodrive after energization. The
servodrive will not work
One switch set to "D" (Dry contact) and another set to "O"
(OSSD). This is a not valid combination and results on a Fault
state (F0160) shown by the servodrive after energization. The
servodrive will not work
Both switches set to OSSD. This configuration must be chosen
when the safety signals are commanded by OSSD (Output
Signal Switching Device), for example, safety relays, as shown
on
Figure 3.5 on page 17
Pin
Name
1
GND
2
STO2
3
SP2
4
STO1
6
5
5
SP1
6
+24Vdc
Figure 3.2: X7 connector description
Description
Description
Reference for +24Vdc PELV/SELV supply
Safety input n°2
Safety signal for STO2 input
Safety input n°1
Safety signal for STO1 input
+24Vdc PELV/SELV supply, provided by the
customer.
Provided by the customer
Figure 3.4