mundoclima AEROTHERM MAM-V9 Serie Manual De Usuario E Instalacion página 129

Monobloc
Ocultar thumbs Ver también para AEROTHERM MAM-V9 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Determine the calculated pre-pressure (Pg) for the
corresponding maximum water volume using the
graph below.
Check that the total water volume in the entire water
circuit is lower than this value. If this is not the case,
the expansion vessel inside the unit is too small for
the installation.
2.8
2.3
1.8
1.3
A1
A2
0.8
0.3
20
70
Maximum water volume(L)
Pre-pressure = pre-pressure of the expansion vessel
Maximum water volume = maximum water volume in the
system
A1 System without glycol for 1-phase 12~16 kW
and 3-phase 12~16 kW unit
A2 System without glycol for the 5/7/9 kW unit
Example 1:
The unit(16kW) is installed 10m below the highest point
in the water circuit. The total water volume in the water
circuit is 50 L. In this example, no action or adjustment is
required.
Example 2:
The unit(16kW) is installed at the highest point in the
water circuit. The total water volume in the water circuit is
150 L.
Result:
Since 150 L is more than 72 L, the pre-pressure must
be decreased (see table above).
The
required
pre-pressure
(H(m)/10+0.3) bar = (0/10+0.3) bar = 0.3 bar
The corresponding maximum water volume can be
read from the graph: approximately 160 L.
Since the total water volume (150 L) is below the
maximum water volume (160 L), the expansion
vessel suffices for the installation.
Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of
the expansion vessel (1.5 bar), following guidelines:
Use only dry nitrogen to set the expansion vessel
pre-pressure.
Inappropriate setting of the expansion vessel
pre-pressure will lead to malfunctioning of the
system. Pre-pressure should only be adjusted by a
licensed installer.
Selecting the additional expansion vessel
If the expansion vessel of the unit is too small for the
installation, an additional expansion vessel is needed.
120
170
is:
Pg(bar)
=
126
calculate the pre-pressure of the expansion vessel:
Pg(bar)=(H(m)/10+0.3) bar
the expansion vessel equipped in the unit should
adjust the pre- pressure also.
calculate the volume needed of the additional expan-
sion vessel:
V1=0.0693*Vwater/(2.5-Pg)-V0
Vwater is volume of water in the system, V0 is volume
of
expansion
vessel
equipped(10~16kW,V0=5L, 5~9kW,V0=2L).
9.4.3 Water circuit connection
Water
connections
must
be
accordance with labels on the outdoor unit, with respect
to the water inlet and water outlet.
CAUTION
Be careful not to deform the unit's piping by
using excessive force when connecting the
piping. Deforming the piping can cause the unit
to malfunction.
If air, moisture or dust gets in the water circuit, problems
may occur. Therefore, always take into account the
following when connecting the water circuit:
Use clean pipes only.
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall to
prevent dust and dirt entering.
Use a good thread sealant for sealing the
connections. The sealing must be able to withstand
the pressures and temperatures of the system.
When using non-copper metallic piping, be sure to
insulate two kind of materials from each other to
prevent galvanic corrosion.
For copper is a soft material,
use
appropriate
tools
connecting the water circuit.
Inappropriate tools will cause
damage to the pipes.
NOTE
The unit is only to be used in a closed water
system. Application in an open water circuit can
lead to excessive corrosion of the water piping:
Never use Zn-coated parts in the water
circuit. Excessive corrosion of these parts
may occur as copper piping is used in the
unit's internal water circuit.
When using a 3-way valve in the water circuit.
Preferably choose a ball type 3-way valve to
guarantee
full
separation
domestic hot water and floor heating water
circuit.
When using a 3-way valve or a 2-way valve in
the
water
circuit.
The
maximum changeover time of the valve
should be less than 60 seconds.
which
the
unit
is
made
correctly
in
for
between
the
recommended

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido