mundoclima AEROTHERM MAM-V9 Serie Manual De Usuario E Instalacion página 152

Monobloc
Ocultar thumbs Ver también para AEROTHERM MAM-V9 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3 HEAT MODE SETTING
HEAT MODE
T1S RANGE
T4HMAX
T4HMIN
dT1SH
SCROLL
:KHQ WKH FXUVRU LV RQ +($7 02'( 8VH
to YES or NON and press OK to enable or disable the
heat mode. When the cursor is on the T1S RANGE, use
WR VFUROO WR <(6 RU 121 DQG SUHVV 2. WR VHOHFW WKH
range of outlet water temperature. When LOW is
selected, the maximum target temperature is 55°C. If
climate-related curve function (corresponds to "weather
temperature set" in the user interface) is enabled, the
curve selected is low temperature curve. When HIGH is
selected, the maximum target temperature is 60°C. If
climate-related curve function (corresponds to "weather
temperature set" in the user interface) is enabled, the
curve selected is high temperature curve.
When the cursor is on T4HMAX、T4HMIN、dT1SH、
G76+ RU WB,17(59$/B+ 8VH
and adjust the parameter.
T4HMAX
is
the
maximum
temperature for heat mode. The unit will not work if the
ambient temperature is higher.
T4HMIN is the minimum ambient operating temperature
for heat mode. The unit will turn off if the ambient
temperature is lower.
The relationship between the operation of the unit and
ambient temperature can be seen in the picture below:
OFF
HEAT
T4HMIN
dT1SH is the temperature difference between T1 and
T1S for starting the unit in heat mode.
When the target outlet water temperature T1S<47, the
unit will turn on or off as described below :
T1S+dT1SH
HEAT
:KHQ WKH WDUJHW RXWOHW ZDWHU WHPSHUDWXUH 76• WKH
unit will on or off as described below:
MIN(T1S+dT1SH,65)
HEAT
dTSH is the temperature difference between Ta (Ta is
the room temperature) and TS for starting the unit when
ROOM TEMP is enabled in TEMP.TYPE SETTING
(refer to 10.7 Field setting/TEMP.TYPE SETTING). Only
when Ta drops to a certain value will the unit turn on, and
the unit will turn off if the Ta high enough. See diagram
below. (only when ROOM TEMP is enabled will this
function be available).
YES
NON
LOW
HIGH
25°C
-15°C
5°C
WR VFUROO
DQG
WR VFUROO
ambient
operating
T4
OFF
T4HMAX
OFF
T1
OFF
T1
149
TS+dTSH
HEAT
t_INTERVAL_H is the compressor start time interval in
heat mode. When the compressor stops running, the next
time that the compressor turns on should be "
t_INTERVAL_H" and one minute later at least.
10.7.4 AUTO MODE SETTING
About AUTO SETTING
Controlling AUTO mode typically consists of the following:
T4AUTOCMIN:setting
the
ambient temperature for cooling
T4AUTOHMAX: setting the maximum operating
ambient temperature for heating
How to set the AUTO mode
To determine whether the AUTO mode is effective, go to
MENU> FOR SERVICEMAN> AUTO MODE SETTING.
Press OK.
The following page is displayed.
4 AUTO MODE SETTING
T4AUTOCMIN
T4AUTOHMAX
SCROLL
Use
and
to scroll and adjust the parameter.
T4AUTOCMIN is the minimum operating ambient
temperature for cooling in auto mode. The unit will turn off
if the ambient temperature is lower when in space cooling
operation.
T4AUTOHMAX is the maximum operating ambient
temperature for heating in auto mode. The unit will turn off
if the ambient temperature is higher when in space
heating operation.
The relationship between heat pump operation and
ambient temperature is described in the picture below.
Heat mode
Heat mode
OFF
by IBH or
by heat
AHS
pump
T4HMIN
T4AUTOHMAX
T4AUTOCMIN
In the picture, AHS is an additional heating source. IBH is
a backup heater in the unit.
10.7.5 TEMP. TYPE SETTING
About TEMP. TYPE SETTING
OFF
Ta
minimum
operating
25°C
17°C
COOL
OFF
T4
T4CMAX

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido