Table B.3: Conducted and radiated emission levels, and additional information
Tabla B.3: Niveles de emisión conducida y irradiada y informaciones adicionales
Tabela B.3: Níveis de emissão conduzida e radiada e informações adicionais
Inverter Model
(With Build-in RFI Filter)
Modelo del Convertidor de Frecuencia
(Con Filtro RFI Interno)
Modelo do Inversor
(Com Filtro RFI Interno
1
CFW501A01P6T2...C3...
2
CFW501A02P6T2...C3...
3
CFW501A04P3T2...C3...
4
CFW501A07P0T2...C3...
5
CFW501A09P6T2...C3...
6
CFW501A12P2T2...C3...
7
CFW501B16P0T2...C3...
8
CFW501B17P0T2...C3...
9
CFW501B19P4T2...C3...
10
CFW501A01P0T4...C3...
11
CFW501A01P6T4...C3...
12
CFW501A02P6T4...C3...
13
CFW501A04P3T4...C3...
14
CFW501A06P1T4...C3...
15
CFW501B02P6T4...C3...
16
CFW501B04P3T4...C3...
17
CFW501B06P5T4...C3...
18
CFW501B10P0T4...C3...
19
CFW501C14P0T4...C2...
20
CFW501C16P0T4...C2...
21
CFW501D24P0T4...C3...
22
CFW501D31P0T4...C3...
Note:
(1) In models 21 and 22, WEG must be consulted in order to check the inverter installations and operating conditions.
Nota:
(1) En los modelos 21 y 22, WEG deberá ser consultada para verificar las condiciones de instalación y operación del convertidor.
Nota:
(1) Nos modelos 21 e 22, a WEG deve ser consultada para verificar as condições de instalação e operação do inversor.
Notes:
For conducted emission category C2, the switching frequency is 5 kHz for models 19 and 20.
For conducted emission C2, in models 19 and 20, use the ferrite 12473659 on the output cables (2 turns).
For conducted emission category C3, the switching frequency is 5 kHz for models 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21 and 22.
For conducted emission category C3, in models 10, 11, 12, 13, 14, 15, 16, 17 and 18, use the ferrite 12480705 on the output
cables (2 turns) and use the ferrite 12480705 on the input cables (2 turns).
For conducted emission C3, in models 19 and 20, use the ferrite 12473659 on the output cables (1 turn).
For conducted emission category C3, in models 21 and 22, use the ferrite 12983778 on the output cables (1 turn) and use the
ferrite 12983778 on the input cables (2 turns).
For Radiated Emission, in models 10, 11, 12, 13 and 14, use shielded cable up to 6 m.
For Radiated Emission, in models 15, 16, 17, 18, 21 and 22, use shielded cable up to 30 m.
For Radiated Emission, in models 19 and 20, use the ferrite 12473659 on the output cables (1 turn). Use shielded cable up to 30 m.
Conducted Emission –
Maximum Motor Cable Length
Emisión Conducida –
longitud Maxima del Cable del Motor
Emissão Conduzida –
Comprimento Máximo do Cabo do Motor
Category C3
Categoría C3
Categoria C3
Contact WEG
Consulte a WEG
Consulte la WEG
6 m
6 m
6 m
6 m
6 m
20 m
20 m
20 m
20 m
30 m
30 m
Contact WEG
(1)
Consulte la WEG
(1)
Consulte a WEG
Appendix B / Anexo B
Radiated
Emission
Emisión Radiada
Emissão Radiada
Category C2
Category
Categoría C2
Categoría
Categoria C2
Categoria
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
20 m
20 m
-
-
CFW501 | 135
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3