Powering up and Startup
5.2.1.2 V V W Control Type (P0202 = 3)
Seq
Indication on the Display / Action
1
Monitoring mode. Press the key ENTER/MENU
st
to enter the 1
level of the programming mode.
2
The PARAM group is selected, press the Keys
 or  until selecting the STARTUP group.
3
When the STARTUP group is selected press
the key ENTER/MENU.
4
Press ENTER/MENU and with the keys  and
 set the value 5, which activates the control
mode V V W.
5
Press ENTER /MENU to save the modification
of P0202.
Figure 5.3: Sequence of the Startup group for V V W control
30 | CFW501
Seq
Indication on the Display / Action
6
Press the key  to proceed with the
Startup of the V V W.
7
If necessary, modify the content of "P0398
– Motor Service Factor".
Press the key  for the next parameter.
8
If necessary, modify the content of "P0399
– Motor rated performance", or press the
key  for the next parameter.
9
If necessary, modify the content of "P0400
– Motor rated voltage", or press the key 
for the next parameter.
10
If necessary, modify the content of "P0401
– Motor rated current", or press the key 
for the next parameter.