Magnetostrictive Linear Position Sensor – Rod Style
6
Calibration procedure (continued)
6.3.2

Adjusting

The detailed procedure for adjustment is
described on page 19 ff.
A new start and/or end value is adjusted. This is
recommended when the magnet cannot be brought to the
null point or end point.
Steps
► Move magnet to the new start position.
► Set the new start value by pressing the buttons.
New start value
Null point
Fig. 6-4:
Adjusting new start position (offset shift)
► Move magnet to the new end position.
► Set the new end value by pressing the buttons.
Before
After
Fig. 6-5:
Adjusting new end position (changing the output gradient)
16
english
6.3.3
Setting start and end values while the system is running.
6.3.4
Restoring the BTL to its factory settings.
6.4
Before
After
Teach-in
1
Null
New end value
point
End point
Fig. 6-6:

Online setting

The detailed procedure for online setting is
described on page 21.

Reset

The detailed procedure for the reset is
described on page 22.

Selecting the calibration procedure

Buttons inactive
1
/
1
2
+
1
2
Buttons active
1
+
1
1
2
2
Reset
Adjusting
2
1
2
End
End
Null
point
point
point
Buttons inactive
1
1
2
+
1
1
1
+
2
1
2
Buttons active
Online
Online
setting
setting
Null point
End point
Selecting the calibration procedure