M06 - SLAVE 01 OUTPUTS (n=1...16)
P06.n.01 Output OUTn function
P06.n.02 Channel number x
P06.n.03 Output normal/reversed
Note: This menu is divided into 16 sections that refer to 16 possible digital outputs OUT01...OUT16, which can be managed by the DCRG8 slave 1;
OUT01..OUT08 on the base device and OUT09...OUT16 on eventual expansion modules installed.
P06.n.01 – Choice of the function for the selected output (see programmable output functions table).
P06.n.02 – Channel number associated with the function programmed in the previous parameter. Example: If the output function is set to Alarm Axx and this
output is to be energised for alarm A31, then set the value 31.
P06.n.03 – Sets the state of the output when P06.n.01 is inactive (OFF): NOR = Output de-energised; REV = Output energised.
M07 – SLAVE 02 OUTPUTS (n=1...16)
P07.n.01 Output OUTn function
P07.n.02 Channel number x
P07.n.03 Output normal/reversed
As previous menu but referred to slave 02.
...
M13 – SLAVE 08 OUTPUTS (n=1...16)
P13.n.01 Output OUTn function
P13.n.02 Channel number x
P13.n.03 Output normal/reversed
As previous menu but referred to slave 08.
OUTPUT FUNCTION TABLE
– The following table shows all the functions that can be attributed to the OUTn programmable digital outputs.
– Each output can be configured so it has a normal or reverse (NOR or REV) function.
– Some functions require another numeric parameter, defined in the channel number x specified by parameter P04.n.02.
– Refer to menu M04 Master outputs and M06...M13 Slave outputs for more details.
FUNCTION
DESCRIPTION
OFF
Output always de-energised
ON
Output always energised
Step x
Capacitor step no.x
Global alarm 1
Energised when global alarm 1 is active
Global alarm 2
Energised when global alarm 2 is active
Global alarm 3
Energised when global alarm 3 is active
Fan
Panel ventilation fan
Manual mode
Active when the controller is in MAN mode
Automatic mode
Active when the controller is in AUT mode
Limit threshold LIMx
Output driven by LIM limits (x= 1...16)
Pulse PULx
Output driven by PUL pulses ( x = 1...6)
Remote variable REMx
Output is remotely controlled by REM variable
Alarms A01-Axx
When the selected Axx alarm is present, the output is activated (xx= 01... alarm number)
Alarms UA1..UAx
When the selected UAx user alarm is present, the output is activated (x=1... 8)
UoM
Default
Range
n=1...8
Step x
Output function table
n=9...16
OFF
n=1...8
OFF/1 – 99
x=1...8
n=9...16
x=1
NOR
NOR - REV
UoM
Default
Range
n=1...8
Step x
Output function table
n=9...16
OFF
n=1...8
OFF/1 – 99
x=1...8
n=9...16
x=1
NOR
NOR - REV
UoM
Default
Range
n=1...8
Step x
Output function table
n=9...16
OFF
n=1...8
OFF/1 – 99
x=1...8
n=9...16
x=1
NOR
NOR - REV
See
G
B
See
See