24
WIRING DIAGRAMS
Standard three-phase installation
MAINS
DCRG8
L1 L2 L3
INPUT
CURRENT
VOLTAGE
100-600V~
1/5A~
1
2 3 4
5 6
7 8
I1 I2 I3 C
L1 L2 L3 N
S1
S2
CT1
FU9
QS1
FU13
LOAD
TC1
THREE-PHASE CONNECTION (default)
Default wiring configuration for standard applications
Voltage measurement
Current measurement
Phase angle offset
Capacitor overload measurement
Parameter setting
NOTE: Recommended fuses for aux supply and voltage measurement inputs: F1A (fast).
Single-phase installation
MAINS
DCRG8
L N
CURRENT
1/5A~
100-600V~
1
2
3
4
5
I1 I2 I3
C
L1 L2 L3 N
S1
CT1
S2
QS1
FU13
LOAD
TC1
SINGLE-PHASE CONNECTION
Wiring configuration for single-phase applications
Voltage measurement
Current measurement
Phase angle offset
Capacitor overload measurement
Parameter setting
NOTE: Recommended fuses for aux supply and voltage measurement inputs: F1A (fast).
OUT
1
2 3 4
5 6
7
8
AUX
SUPPLY
110-415V~
110-250V=
9 10 11
19
12 13 14 15 16 17 18
20 21 22
nc A1 A2
FU10
FU1
R
FU12
FU11
KM1
KM2
R
K1
1 ph-to-ph voltage reading L1-L2
L3 phase
Between V (L1-L2 ) and I (L3)
90°
1 reading calculated on L1-L2
P02.03 = Three-phase P02.22 = LV
P02.04 = L3
P02.06 = L1-L2
1
2
3
4
INPUT
AUX
VOLTAGE
SUPPLY
110-415V~
110-250V=
6
7
8
9 10 11
12 13 14 15 16 17 18
19
nc
A1 A2
FU9
FU1
FU11
FU12
FU10
KM1
R
K1
1 phase voltage reading L1-N
L1 phase
Between V (L1-N ) and I (L1)
0°
1 reading calculated on L1-N
P02.03 = Single-phase P02.22 = LV
P02.04 = L1
P02.06 = L1-N
FU8
FU2
R
R
KM8
R
R
K2
K8
OUT
5
6
7
8
20 21 22
FU2
FU8
Contattori BFK...
BFK... contactors
KM2
KM8
R
R
K8
K2
G
B
Contattori BFK...
BFK... contactors