M14 – PROGRAMMABLE INPUTS (INPn, n=1...8)
P14.n.01 INPn input function
P14.n.02 Channel number x
P14.n.03 Type of contact
P14.n.04 Delay ON
P14.n.05 Delay OFF
Note: This menu is divided into 8 sections that refer to 8 possible digital inputs
P14.n.01 – Choice of the function for the selected input (see programmable input functions table).
P14.n.02 – Channel number associated with the function programmed in the previous parameter. Example: If the input function is set to Cxx commands menu
execution and you want this input to perform command C07 of the commands menu, then set the value 7.
P14.n.03 – Select the type of contact: NO (Normally Open) or NC (Normally Closed).
P14.n.04 – Contact closing delay for selected input.
P14.n.05 – Contact opening delay for selected input.
INPUT FUNCTIONS TABLE
– The following table shows all the functions that can be attributed to the INPn programmable digital inputs.
– Each input can be set for an reverse function (NO - NC), delayed energising or de-energising at independently set times.
– Some functions require another numeric parameter, defined in the channel number x specified by parameter P14.n.02.
– Refer to menu M14 Programmable inputs for more details.
FUNCTION
DESCRIPTION
OFF
Disabled input
Configurable
Free user configurable input INPx. Used for instance to generate a user alarm UA or to count on a CNT counter
Automatic mode
When active, switches system to AUT mode
Manual mode
When active, switches system to MAN mode
Select cosphi setpoint x
When active, selects the cosphi setpoint x (x=1...3)
Keyboard lock
Locks front keyboard
Settings lock
Locks access to setup menu and commands menu
Alarm inhibition
Selectively disables alarms having inhibit property set to ON.
M15 – PASSWORD
P15.01
Enable password
P15.02
User level password
P15.03
Advanced level password
P15.04
Remote access password
P15.01 – If set to OFF, password management is disabled and anyone has access to the settings and commands menu.
P15.02 – With P15.01 enabled, this is the code number to access user level. See Password access chapter.
P15.03 – As per P15.02 but referred to Advanced level access.
P15.04 – If set to a numeric value, this becomes the code to specify via serial communication before sending commands from a remote control site.
UoM
Default
Range
OFF
(see Input functions
table)
OFF
OFF / 1...99
NO
NO/NC
s
0.05
0.00-600.00
s
0.05
0.00-600.00
UoM
Default
Range
OFF
OFF-ON
1000
0-9999
2000
0-9999
OFF
OFF/1-9999
G
B
15