8. Installing the grille
Fig. 8-6
Fig. 8-8
Fig. 8-9
A
Fig. 8-10
8.3.2. Temporary installation of the grille (Fig. 8-6)
• Align the electric component box of the main unit and the receiver of the grille, and
then temporarily secure the grille using the bell shaped holes.
8.3.3. Securing the grille (Fig. 8-7)
• Secure the grille to the main unit by tightening the previously installed two screws
(with captive washer) as well as the two remaining screws (with captive washer).
Fig. 8-7
8.3.4. Wire connection (Fig. 8-8)
• Be sure to connect the unit to the connector (white:10-pole/red:9-pole). Next, at-
tach the white glass tube that comes with the main unit so that the tube covers the
connector. Close the opening of the glass tube with the band.
• Make sure that there is no slack in the each lead wire at the fastener on the
grille.
8.4. Locking the up/down airflow direction (Fig. 8-9)
The vanes of the unit can be set and locked in on up or down orientation depending
upon the environment of use.
• Set according to the preference of the customer.
The operation of the fixed up/down vanes and all automatic controls cannot be
performed using the remote controller. In addition, the actual position of the vanes
may differ from the position indicated on the remote controller.
1 Turn off the main power switch.
A Button
B Vane motor
2 Disconnect the connector for the vane motor of the vent that you want to lock.
C Up/down vanes
D Connector
3 To adjust the desired airflow direction, slowly move the up/down vanes within the
Specified range
E Measurement standard
position of grille
• The vanes can be set between 21 and 30 mm.
F Up/down vanes
Do not set the up/down vanes passed the specified range. Condensation could
form on and drop from the ceiling, or the unit could malfunction.
* Make sure that the lead wiring of the grille does not get pinched between the
grille and the main unit.
A Main unit
B Electric component box
C Screw with washer (for temporary use)
D Screw with washer (Accessory)
E Grille
F Bell shaped hole
G Receiver (For SLZ-KA·VAL(2))
* Make sure that there are no gaps between the main unit and the grille or the
grille and the ceiling.
A Ceiling
B Main unit
C Grille
D Make sure that there are no gaps.
A Fastener (Accessory)
B White glass tube
C Connector of the main unit
D Connector of the grille
E Band (Accessory)
F Receiver (For SLZ-KA·VAL(2))
Injuries and or an electrical shock may occur while the fan of the unit is rotating.
(While pressing the button, remove the connector in the direction indicated by
the arrow as shown in the diagram.) After removing the connector, insulate it with
tape.
specified range. (Fig. 8-10)
Up/down airflow
Horizontal 30°
Downward 45° Downward 55° Downward 70°
direction
A (mm)
21
Caution:
25
28
30
11