Analogue Inputs - LU-VE Emeritus LU1W Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

MODBUS
MODBUS
Parameter Name and
Register
Register
Description
Base 0
Base 1
PH46
Logic DI6 ramps/tank
0x0828
2089
water discharge
PH48
Enable DI8 enable
0x0836
2103
adiabatic panels
PH49
Logic DI8 enable adiabatic
0x0837
2104
panels
Digital inputs, for which there are no enabled parameters in the above list (silent mode, pump alarm, discharge), are
enabled through different parameters; for details, see sections on specific functions below.
2.3
2.3.1
Probe Types
The control probe type varies automatically according to the exchanger type: NTC temperature probe (10kΩ at 25°C)
for dry coolers and 4-20 mA pressure probe for condensers. The probe in use can be viewed at the PH19 read-only
parameter.
The type of additional probes/transducers, if present, is defined by the following parameters (factory set):
-
Parameter PH21: supply water pressure probe for sprayers
-
Parameter PH24: supply water pH probe for spray/adiabatic panel resources
-
Parameter PH25: supply water conductivity probe for spray/adiabatic panel resources
-
Parameter PH23: supply water flowmeter model for measuring flow rate for adiabatic panels
The full-scale of the condensing pressure and water pressure probes of the sprayers can be modified using the PH11
and PH13 parameters.
Attention: when replacing the pressure probes with probes having different full-scales, change the relative
parameters; on the other hand, do not modify the pressure probe full-scale parameters unless warranted by a real
full-scale change. Failure to comply with these instructions can lead to adjustment problems, blockage or poor
management of the spray system.
The transducer basepoints of pH and conductivity are factory set and correspond to PH14, PH15, PH16, PH17.
PARAMETER
NAME
READ ONLY
Main Control Probe:
PH19
0 = NTC
1 = 4..20mA
READ ONLY
Water spray pressure probe:
PH21
0 = 0-10V
1 = 4..20mA
LU1W - User Manual
Data Type and Notes
0 = N.O. contact,
1 = N.C. contact
- unsigned short int
0 = disabled,
1 = enabled
- unsigned short int
0 = N.O. contact,
1 = N.C. contact
- unsigned short int

Analogue Inputs

DESCRIPTION
Default
value
0
0
0
DEFAULT
MIN
VALUE
VALUE
NTC
NTC
0-10V
0-10V
17
Decimal
Min
Max
positions
0
1
0
1
0
1
MAX
UM
VALUE
-
4..20mA
-
4..20mA
REV.1.1 – 07/11/2017 - ENG
MODBUS
Register
Type
0
Holding
0
Holding
0
Holding
MENU
ADVANCED →
VARIOUS
ADVANCED →
VARIOUS

Publicidad

Tabla de contenido
loading

Tabla de contenido