SKF: communication error
•
FB: Inverter error
•
TFM: high engine temperature
•
HLL: hall probe
•
BLK: rotor locked
•
UzLow: low voltage DC
MODBUS Registers
MODBUS
MODBUS
Name and Description
Register
Register
Parameter
Base 0
Base 1
PackedAlarm1
Alarms in progress - word
0x0300
769
1
PackedAlarm2
Alarms in progress - word
0x0301
770
2
PackedAlarm3
Alarms in progress - word
0x0302
771
3
fan1AL
0x0304
773
Alarms in progress fan 1
fan2AL
0x0305
774
Alarms in progress fan 2
fan3AL
0x0306
775
Alarms in progress fan 3
fan4AL
0x0307
776
Alarms in progress fan 4
fan5AL
0x0308
777
Alarms in progress fan 5
fan6AL
0x0309
778
Alarms in progress fan 6
fan7AL
0x030A
779
Alarms in progress fan 7
LU1W - User Manual
Default
Data Type and Notes
value
**
- word 16 bit
**
- word 16 bit
**
- word 16 bit
BIT0 = PHA; BIT1 = COM;
BIT2 = TFE; BIT3 = SKF;
BIT4 = FB; BIT5 = TFM;
BIT6 = HLL; BIT7 = BLK;
BIT12 = Uzlow
- word 16 bit
BIT0 = PHA; BIT1 = COM;
BIT2 = TFE; BIT3 = SKF;
BIT4 = FB; BIT5 = TFM;
BIT6 = HLL; BIT7 = BLK;
BIT12 = Uzlow
- word 16 bit
BIT0 = PHA; BIT1 = COM;
BIT2 = TFE; BIT3 = SKF;
BIT4 = FB; BIT5 = TFM;
BIT6 = HLL; BIT7 = BLK;
BIT12 = Uzlow
- word 16 bit
BIT0 = PHA; BIT1 = COM;
BIT2 = TFE; BIT3 = SKF;
BIT4 = FB; BIT5 = TFM;
BIT6 = HLL; BIT7 = BLK;
BIT12 = Uzlow
- word 16 bit
BIT0 = PHA; BIT1 = COM;
BIT2 = TFE; BIT3 = SKF;
BIT4 = FB; BIT5 = TFM;
BIT6 = HLL; BIT7 = BLK;
BIT12 = Uzlow
- word 16 bit
BIT0 = PHA; BIT1 = COM;
BIT2 = TFE; BIT3 = SKF;
BIT4 = FB; BIT5 = TFM;
BIT6 = HLL; BIT7 = BLK;
BIT12 = Uzlow
- word 16 bit
BIT0 = PHA; BIT1 = COM;
BIT2 = TFE; BIT3 = SKF;
BIT4 = FB; BIT5 = TFM;
BIT6 = HLL; BIT7 = BLK;
BIT12 = Uzlow
- word 16 bit
100
Min
Max
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
REV.1.1 – 07/11/2017 - ENG
MODBUS
Decimal
Register
positions
Type
-
Input
-
Input
-
Input
-
Input
-
Input
-
Input
-
Input
-
Input
-
Input
-
Input