4. KEYPAD (HMI) AND BASIC PROGRAMMING

4.1 INTEGRAL KEYPAD - HMI-CFW700

The integral keypad can be used to operate and program (view / edit all parameters) of the
CFW700 inverter. There are two operation modes in the keypad: monitoring and programming.
The key functions and display indications of the keypad may change according to the operation
mode. The programming mode consists of three levels.
- When in monitoring mode: press this key to increase the
speed.
- When in programming mode, level 1: press this key to go
back to the previous group.
- When in programming mode, level 2: press this key to go
to the next parameter.
- When in programming mode, level 3: press this key to
increase the parameter value.
- When in programming mode,
level 1: press this key to go
back to the monitoring mode.
- When in programming mode,
level 2: press this key to go
back to the level 1.
- When in programming mode,
level 3: press this key to
cancel the new value (the
value will not be saved) and
it will return to level 2 of the
programming mode.
- Press this key to define the
motor rotation.
This option is active when:
P0223 = 2 or 3 in LOC and/
or
P0226 = 2 or 3 in REM.
- Press this key to change
between LOCAL and
REMOTE mode.
This option is active when:
P0220 = 2 or 3.
- Press this key to accelerate the motor up to the speed set in P0122. The motor speed is maintained
while the key is pressed. When the key is released the motor decelerates up to its complete stop.
This function is active when all the following conditions are met:
1. Start/Stop = Stop;
2. General Enable = Active;
3. P0225 = 1 in LOC and/or P0228 = 1 in REM.
NOTE!
It is necessary to set the password at P0000 for parameter modification;
otherwise the parameters contents can only be viewed.
The default password for P0000 is 5. It is possible to change the password
at P0200. Refer to the CFW700 Programming and Troubleshooting manual.
Keypad (HMI) and Basic Programming
- When in monitoring mode: press this key to
decrease the speed.
- When in programming mode, level 1: press this key
to go to the next group.
- When in programming mode, level 2: press this key
to go back to the previous parameter.
- When in programming mode, level 3: press this key
to decrease the parameter value.
- When in monitoring mode: press this key to enter in
the programming mode.
- When in programming mode, level 1: press this key
to select the desired parameter group – it shows
the parameters of the selected group.
- When in programming mode, level 2: press this key
to show the parameter – it shows the parameter
value for its modification.
- When in programming mode, level 3: press this key
to save the new parameter value – it returns to level
2 of the programming mode.
- Press this key to accelerate the motor according to
the acceleration ramp time.
This option is active when:
P0224 = 0 in LOC and/or
P0227 = 0 in REM.
- Pressione esta tecla para desacelerar o motor com
tempo determinado pela rampa de desaceleração.
Ativa quando:
P0224 = 0 em LOC e/ou
P0227 = 0 em REM.
Figure 4.1: Operator keys
- English -
CFW700 | 25

Publicidad

Capítulos

Tabla de contenido
loading