The Function 2 of the Application at parameters P0251 or P0254 represents the value of the
PID Feedback;
The Function 1 of the Application at parameters P0263 or P0270 represents the value of the
Manual/Auto command;
The Function 1 of the Application at parameters P0275 to P0279 represents the VP>VPx
logical condition;
The Function 2 of the Application at parameters P0275 to P0279 represents the VP<VPy
logical condition.
The PID setpoint can receive an analog input signal (AI1 or AI2). It is necessary to set P1016
to 1=AIx and select which analog input will be used. The analog inputs are set at P0231 (AI1)
or P0236 (AI2) and it is necessary to program it to 5=Function 1 of the Application in order to
enable the analog inputs for the operation. The following alarm message will be displayed in
case it is not properly done: "A770: Set AI1 or AI2 for Function 1 of the Application".
The PID setpoint value can be presented via analog output AO1 or AO2. It is necessary to
set P0251 (AO1) or P0254 (AO2) to 17 = Function 1 of the Application. The full scale value of
the variable is 100.0 % and corresponds to 10 V or 20 mA.
The PID feedback can receive an analog input signal (AI1 or AI2). It is necessary to set P0231
(AI1) or P0236 (AI2) to 6 = Function 2 of the Application in order to enable the analog inputs for
the operation. The following alarm message will be displayed in case it is not properly done:
"A772: Set AI1 or AI2 for Function 2 of the Application".
In case the analog inputs (AI1 and AI2) are programmed with the same function, PID Setpoint
or Feedback, the following alarm message will be displayed and the application will not be
enabled: "A774: AI1 and AI2 were set for the same function".
The value of the PID feedback can be presented via analog output AO1 or AO2. It is necessary
to set P0251 (AO1) or P0254 (AO2) to 18 = Function 2 of the Application. The full scale value of
the variable is 100.0 % and corresponds to 10 V or 20 mA.
The Manual/Auto control is done by a digital input (DI1 to DI8). It is necessary to set one of the
DI parameters (P0263 to P0270) to 20 = Function 1 of the Application. If more than one digital
input is set for this function, the logic operation will consider only the command of the high
priority level digital input, where: DI1>DI2>DI3>DI4>DI5>DI6>DI7> DI8. If any of the digital inputs
is set, the PID controller will work only in automatic (Auto) mode.
The Manual/Auto input is active when it is in 24 V indicating automatic control and it is inactive
in 0 V indicating manual operation.
The digital outputs (DO1 to DO5) can be programmed to trigger comparison logics with the
process variable (PV). In order to do that, it is necessary to set one of the DO's parameters
(P0275 to P0279) to 34 = Function 1 of the Application (VP>VPx) or 35 = Function 2 of the
Application (VP<VPy).
Keypad (HMI) and Basic Programming
- English -
CFW700 | 29