Step
Action/Display Indication
9
I f n e c e s s a r y, c h a n g e " P 0 2 9 8 –
Application" parameter. This change
will affect P0156, P0157, P0158, P0401,
P0404 and P0410 (this last one only if
P0202 = 0, 1 or 2 - V/f modes). The
time and level of the IGBT overload
protection will also be affected.
Press the
key to the next parameter.
If necessary, change "P0202 – Control
10
Type" parameter. This guide will only
show the setting for P0202 = 0 (V/f 60
Hz) or P0202 = 1 (V/f 50 Hz). Refer to
the Programming and Troubleshooting
Manual for other settings (V/f Adjustable,
V V W or Vector Modes).
Press the
key to the next parameter.
11
If necessary, change "P0398 – Motor
Service Factor" parameter. This change
will affect the current and the time of the
motor overload protection operation.
Press the
key to the next parameter.
Figure 5.1 (cont.): Oriented Start-up
First Time Power-Up and Start-Up
Step
Action/Display Indication
12
If necessary, change "P0400 – Motor
Rated Voltage" parameter. This change
corrects the output voltage by the factor
"x = P0400/P0296".
Press the
If necessary, change "P0401 – Motor
13
Rated Current" parameter. This change
will affect P0156, P0157, P0158 and
P0410.
Press the
14
If necessary, change "P0404 – Motor
Rated Power" parameter. This change
will affect P0410.
Press the
- English -
key to the next parameter.
key to the next parameter.
key to the next parameter.
CFW700 | 47