The START electronic control unit can be used to control 1 single-phase, 230Vac motor, or a three-phase 400Vac motor with power
not exceeding 750W for the single-phase motor and 2200W for the three-phse motor.
This control unit operates with "Hold-to-run" mode.
The OPEN - CLOSED push-buttons must be kept pressed for the entire operation time.
Do not use controls with self-hold contact.
The control devices should be placed near the opening.
The operator who controls the gate/door must have full sight of the door or gate and must not stand in a dangerous area.
a) The wire connections and the operating logic should be in compliance with regulations in force.
b) The cables featuring different voltage should be physically separated, or adequately insulated by an additional insulation of at
least 1 mm.
c) The cables should be further fastened in proximity to the terminals.
d) Check all connections before powering the unit.
e) Normally Closed (N.C.) inputs which are not in use should be short-circuited
f) On the power supply mains a omnipolar switch must be provided for, with an opening distance of the contact equal or higher
than 3 mm. Check that an adequate differential switch and an adequate over-current protection are provided at the beginning of
the wire system.
Terminal No.
Function
Single-phase
1-2
power supply
Three-phase
1-2-3
power supply
4-5-6
Motor
7-8
Blinker
8-9
AUX
Auxiliary
10-11
capacitor
12-13
STOP
14-15
SWO
16-17
OPEN
18-19
SWC
20-21
CLOSE
22-23
SAFETY
Selection of
24-25-26
mains power
supply
START Control Unit
IMPORTANT:

GENERAL WARNINGS

INPUT/OUTPUT FUNCTIONS
START Control Unit
Description
Input, single-phase, mains power supply, 230Vac/50Hz (1-L / 2-N)
Input, three-phase, mains power supply, 400Vac/50Hz (1-R / 2-S / 3-T).
230Vac motor connection - single-phase:
4-Phase+capacitor / 5-Common / 6-Phase+capacitor
400Vac - three-phase motor connection:
4-U / 5-V / 6-W
Check the correct position of the jumper to select voltage to terminals 24-25-26
Connection of blinker, 230Vac/40W max.
WARNING: Output, 230Vac 0,2 A max.
N.O. free contact (10A max) for pickup, auxiliary capacitor.
See wire diagram. At every start, the contact closes for 1.5s.
Input, STOP push-button (N.C. contact)
Input, OPEN limit switch (N.C. contact)
Input, OPEN push-button (N.O. contact)
Input, CLOSE limit switch (N.C. contact)
Input, CLOSE push-button (N.O. contact)
Connection of emergency stop. WARNING: mains voltage.
Remove the jumper and connect a switch suited to the mains power.
Selection of power supply voltage, to be short-circuited:
24 and 25 for three-phase power supply (400Vac)
25 and 26 for single-phase power supply (230Vac)