Cable Termination:
Run twisted pair cable to the Panel from the wall outlets. Strip approximately 3" of outer
jacket from the cable. Match the color coding of the wires to the colors on the 110 IDC color
coded wire termination diagram. All four pairs of each cable must be terminated. Make
sure to terminate Category 5e wire to Category 5e ports and Category 6 wire to Category 6
ports. Slide each wire into the wire holder in its associated channel.
NOTE: The TIA-570-B Residential Wiring Standard calls for T568A wiring termination.
Certain building installations may require T568B termination. To use T568B termination, flip
the color coded wire termination diagram over and wire according to the color code shown
for T568B. Wall Outlets must be wired to match the chosen termination standard.
For voice, each pair of wires corresponds to one line from the phone company when wire is
used to distribute phone service. (Line 1=Blue pair, Line 2=Orange pair, Line 3=Green pair,
Line 4=Brown pair.) (Figure 1)
Using Plastic Tool Provided:
1. Push the appropriate wire into the color designated 110 IDC slot with the tool (Figure 2).
2. Trim excess wire with diagonal cutters (Figure 3).
Using professional Punch Tool:
1. Orient tool with cutting blade as shown (Figure 4).
2. Push straight down until tool seats and trims wire, making a clicking noise.
1
3) MOUNTING
After terminating all cables and all wires, slide the panel up and pull straight out and away
from the enclosure to release the installation hooks. Twist the patch panel 180° horizontally
and align the mounting pins with the grid holes in the back of the enclosure. Feed excess
cable into the wall cavity and with the mounting pin plungers in the "out" position, press the
unit into the grid in the desired location, secure by pushing the plungers in. Dress service
loop of wires along the side of the enclosure.