= Stop drive before changing this parameter.
No.
Parameter
P037 [Stop Mode]
Active stop mode for all stop sources [e.g. run
forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted.
Important: I/O Terminal 01 is always a coast to
stop input except when P036 [Start Source] is set
for "3-Wire" control. When in three wire control, I/O
Terminal 01 is controlled by P037 [Stop Mode].
P038 [Speed Reference]
Sets the source of the speed reference to the
drive.
Important: When A051 or A052 [Digital Inx Sel] is
set to option 2, 4, 5, 6, 13 or 14 and the digital
input is active, A051, A052, A053 or A054 will
override the speed reference commanded by this
parameter. Refer to Chapter 1 of the PowerFlex
40P User Manual for details.
P039 [Accel Time 1]
Sets the rate of accel for all speed increases.
P040 [Decel Time 1]
Sets the rate of decel for all speed decreases.
P041 [Reset To Defalts]
Resets all parameter values to factory defaults.
P042 [Voltage Class]
Sets the voltage class of 600V drives.
P043 [Motor OL Ret]
Enables/disables the Motor Overload Retention function.
Advanced Display Group Parameters
No.
Parameter
d301 [Drive Status 2]
d302 [Fibers Status]
d303 [Slip Hz Meter]
d304 [Speed Feedback]
d305 [Speed Feedback F]
d306 [Encoder Speed]
d307 [Encoder Speed F]
d308 [Units Traveled H]
d309 [Units Traveled L]
Program Group Parameters
Refer to the PowerFlex 40P User Manual supplied with the drive for
complete listing of parameters.
Min/Max
Display/Options
0/9
0 = "Ramp, CF"
1 = "Coast, CF"
2 = "DC Brake, CF"
3 = "DCBrkAuto,CF"
4 = "Ramp"
5 = "Coast"
6 = "DC Brake"
7 = "DC BrakeAuto"
8 = "Ramp+EM B,CF"
9 = "Ramp+EM Brk"
(1)
1/9
1 = "InternalFreq"
2 = "0-10V Input"
3 = "4-20mA Input"
4 = "Preset Freq"
5 = "Comm Port"
6 = "Stp Logic"
7 = "Anlg In Mult"
8 = "Encoder"
9 = "Positioning"
0.0/600.0 Secs
0.1 Secs
0.0/600.0 Secs
0.1 Secs
0/1
0 = "Ready/Idle"
1 = "Factory Rset"
2/3
2 = "Low Voltage" (480V)
3 = "High Voltage" (600V)
0/1
1 = "Enabled"
Min/Max
Display/Options
0/1
1
0/1
1
0.0/25.0 Hz
0.1 Hz
0/64000 RPM
1 RPM
0.0/0.9
0.1
0/64000
1
0.0/0.9
0.1
0/64000
1
0.00/0.99
0.01
(1)
(1)
(1)
(1)
Stop input also clears active fault.
Default
0
5
10.0 Secs
10.0 Secs
0
3
0 = "Disabled"