SMA SUNNY HIGHPOWER PEAK1 Instrucciones De Instalación página 37

Ocultar thumbs Ver también para SUNNY HIGHPOWER PEAK1:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

SMA Solar Technology AG
Events Caused by the Self-Test
ID
Description
100
PV input current is negative. Sensor fault. Check the polarity of the PV system.
264,
Measurement circuit test failed.
266
272
PV overvoltage protection device error.
Inverter will continue operation without
overvoltage protection.
273
Grid overvoltage protection device
error. Inverter will continue operation
without overvoltage protection.
274
Overvoltage protection device status
unknown.
350–
Residual-current monitoring unit (RCMU)
352
self-test failed.
353
Current sensor test failed.
356–
Transistor and relay test failed or inverter
361
relay has failed (contact assumed
welded).
366
Residual-current monitoring unit (RCMU)
self-test failed.
Table 4.5 Events caused by the self-test
Installation Guide
Measure
If polarity is correct, call Service.
Restart the inverter. If the event persists,
call Service.
Replace PV overvoltage protection
device. See SPD replacement
instructions for details.
Replace PV overvoltage protection
device. See SPD replacement
instructions for details.
Restart the inverter. If the event persists,
call Service.
Contact the service.
Contact the service.
Contact the service.
Contact the service.
4  Service
DNO SMA
Service
Line
-
x
-
x
-
x
-
x
-
x
-
x
-
x
-
x
-
x
SHP75-10-IA-xx-15
PV
-
-
-
-
-
-
-
-
-
37

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido