Hydraulic Circuit; Internal Hydraulic Circuit (Anr-H°); Anr - (Ha - Hk); Anr - (Hp) - AERMEC ANR Serie Manual Del Usuario

Bombas de calor aire / agua, de alta eficiencia ventiladores axiales
Ocultar thumbs Ver también para ANR Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. 1 . 1
INTERNAL HYDRAULIC
CIRCUIT ANR - (H°)
The internal hydraulic circuit of the ANR
H° is composed of (see Fig. 6.2. 1 ):
- Fitted water filter
- Exchanger pressure switch
- Plate evaporator
- Water inlet/outlet temperature probes

6. 1 .2 ANR - (HA - HK)

The internal hydraulic circuit of the ANR
HA-HK is composed of (see Fig. 6.2.2):
- Pump
- Expansion tank
- Water storage tank
- Safety valve
- Air bleed valve

6. 1 .3 ANR - (HP)

The internal hydraulic circuit of the ANR
HP is composed of (see Fig. 6.2.3):
- Pump
- Expansion tank
- Safety valve
- Air bleed valve
6. 1 .4 EXTERNAL HYDRAULIC
CIRCUIT ANR (NOT
SUPPLIED)
The choice and the installation of com-
ponents external to the ANR is up to the
installer, who must operate according
to the rules of good technical design
and in compliance with the regulations
in force in the country of destination
(Ministerial Decree 329/2004).
In any case, we recommend installing
the following:
- Air priming/bleed unit
- Anti-vibration joints
- Pump(s) if necessary
- Expansion tank
- Cutoff cocks
- Pressure gauges
40
6

HYDRAULIC CIRCUIT

6.2. 1 INTERNAL HYDRAULIC CIRCUIT STANDARD VERSION (H)

1
2
LEGEND
1 Fitted water filter
2 Differential pressure switch
3 Plate evaporator (with electrical resistor as standard supply)
4 Water inlet/outlet temperature probes SIW SUW
6.2.2 INTERNAL HYDRAULIC CIRCUIT WITH PUMP AND STORAGE TANK (HA-HK)
1
LEGEND
1 Storage tank
2 Differential pressure switch
3 Plate evaporator (with electrical resistor as standard
supply)
4 Water inlet/outlet temperature probes SIW SUW
5 Expansion tank
6 Pump
7 Fitted water filter
8 Safety valve (calibrated 6 bar)
6.2.3 INTERNAL HYDRAULIC CIRCUIT WITH PUMP (HP)
1
LEGEND
1 Differential pressure switch
2 Plate evaporator (with electrical resistor as standard
supply)
3 Water inlet/outlet temperature probes SIW SUW
4 Expansion tank
5 Pump
6 Fitted water filter
7 Safety valve (calibrated 6 bar)
3
4
5
2
2
3
4
3
4
6
8
7
5
7
6

Publicidad

Tabla de contenido
loading