DIMENSIONS INCHES (MM)
2.18
(55)
1.32
(34)
IMPORTANT SAFETY INSTRUCTIONS
• WARNING—Be very careful when working with batteries. Lead acid
batteries can generate explosive gases, and short circuits can draw
thousands of amps from the battery. Read all instructions provided
with the battery.
• Do not exceed the voltage or current ratings of the controller. Use
only with a 12 volt or 24 volt battery.
• DO NOT short circuit the PV array or load while connected to the
controller. This will DAMAGE the controller.
• The controller should be protected from direct sunlight. Ensure
adequate space for air flow around the controller.
• Pressure terminal connectors are not required. Use only copper wire
with minimum 75°C insulation rating and between 5.2 mm² (10 AWG)
and 2.1 mm² (14 AWG) gage.
• The negative system conductor should be properly grounded.
Grounding should comply with local codes.
INSTALLATIONS IN HAZARDOUS
The SunSaver family of charge controllers have been listed to UL1604
and CSA 22.2 No. 213-M1987 for use in Class I, Division 2, Groups A,
B, C and D hazardous locations. In order to comply with the UL and
1.00
(25)
4 MOUNTING HOLES ø0.20 (5.0)
0.50
(13)
(CLASSIFIED) LOCATIONS
6.00 (152)
5.50 (140)
3