Installation and Connection
1.1.5 Voltage Input /
External Power
Supply
GB
1.1.6 Digital Outputs
GB
1.1.7 Relay Outputs
1.1.8 Analog Outputs
1.1.9 Voltage Output
GB- 6
The supply of the control circuit through an external voltage source keeps
the control in operational condition even if the power stage is switched off.
To prevent undefined conditions at external power supply the basic
procedure is to first switch on the power supply and after that the inverter.
X2A
10 11
X2A
10
In case of inductive load on the relay outputs a protective wiring must be
provided (e.g. free-wheeling diode, see Part 1.2.6)!
X2A
The voltage output serves for the setting of the digital inputs as well as for
the supply of external control elements. Do no exceed the maximum
output current of 100 mA.
X2A
10
17 18 19 20
21 22 23
+
20...30V ±0% / 1 A DC
smoothed
18 19 20
21 22 23
X2A
24 25 26
27 28 29
max. 30 VDC / 0,01...1 A
1 2 3 4 5 6 7 8 9
0...±10 VDC
5 mA
18 19 20
21 22 23
+
ca. 24VDC / max. 100 mA
approx.
PE
PE
A total of max.
50 mA DC for
both outputs
PE
PE
PE
-