Annex 4:
Transmitters / Emetteurs / Polung der Anschlüsse / Emettitori d'impulsi / Emisores / Connector aansluiting /
Vericiler / Transmissores
Compact DN25/DN40/DN50
LF
Binder plug 6 pins (LF, MF, HF)
(Rear view of the plug)
3
4
6
5
Unless on the nameplate noted the following electrical parameters shall be considered:
Characteristics
Power rating
Voltage (Break-down)
Current (Switching)
Capacitance and Inductance
Operation temperature range
** Following recommend values Low Frequency Pulse Transmitters do not have any potential sources of ignition and shall
be not marked according to directive 2014/34/EU
The device is free to be used in ATEX area as it is a simple apparatus as defined in EN 60079-11 §5 7
*** Proximity detectors conform to EN60947-5-6 (NAMUR) standard
Characteristics
Contact power rating
Voltage (Break-down)
Current (Switching)
Operation temperature range
 
 
Installation of the Cyble sensor
1) Mounting
Note: For the plugging of the LF, HF and anti-tampering, please report to the name plate of the meter
62
LF,
HF
2
1
Low Frequency Transmitter (reed contact)
For Non ATEX pro-
ducts
Max 10 W
Max 180 V dc
Max 50 mA
C=0F, L=0H
-30°C to +60°C
 
2) Screwing (Max torque: 0,25Nm)
DN50/DN80/DN100/DN150
LF
Binder plug 3 pins (HF)
(Rear view of the plug)
3
For ATEX products **
intrinsically safe circuits EN
60079-0/-11
Max 120 mW
Max 15 V dc
Max 50 mA
C=0F, L=0H
-30°C to +60°C
Low Frequency Transmitter (Cyble Module)
Max 1 W
Max 14 3 V dc
Max 50 mA
-25°C to +55°C
HF
LF,
MF
2
1
High & Medium Frequency
Transmitter (inductive)
For ATEX products ***
intrinsically safe circuits EN
60079-0/-11
Max 64 mW
Max 15 V dc
Max 50 mA
C= 90ƞF, L = 250 µH
-30°C to +60°C
3) Sealing