3.5.1. Synopsis of programme for classing parameters
Long
Long
Lo.SC ............ Minimum setpoint value
PL.1 or PL.2 ............ Limitation of power 1 or 2
Con.A ............ Type of control action
A1.md ............ Type of alarm
A2.md
(Idem A1.md)
C.CYC ............ Cycle time
Note 1 : The order of this sequence as well as the level that each parameter belongs to can be modified by means of the utility
programme (see Ch 3.6). The unused parameters can be removed from the sequence (level 3).
Note 2 : Press
for more than 4 seconds to access the parameter of the higher level (symbol : long
Normal display .... Input value or setpoint value
ASP .1 ............ Value of the alarm or timer
Time (if A1SF = to.on or to.oF)
rAmP ............ Ramp value
oFSt ............ Pb offset (ti=0)
ASP .2 ............ Value of the alarm
ShiF ............ Display offset
Pb ............ Proportional band
ti ............. Integrale time
td ............ Derivative time
AhY . ............
1
Hysteresis of alarm 1
AhY .2 ............ Hysteresis of alarm 2
hYSt ............ Hysteresis of ON/OFF control
Addr ............ Address for communication
hi.SC ............ Maximum setpoint value
inPt ............ Selection of type of input
unit ............ Selection of the unit
rESo ............ Resolution of display
or
A1.SF ............ Special alarm function
.............Type of alarm
or
A2.SF ............Special alarm function
CYC ............ Cycle time
or
or
C.PB ............
Prop. channel 2
............Dead band
d-B
or
or
of the low value at the top of the scale
Absolute alarm
or
Following or symmetrical alarm
Timer
or
0...55,55°C/min (0...99,99°F/min)
or
0...100%
Absolute alarm
or
Following or symmetrical alarm
or
-111...+111°C (-199,9...+199,9°F)
or
0...200°C (0...360°F) 0 : ON-OFF
or
0...3600 s
or
0...1000 s
or
0...11°C (0,1...19,9°F)
0...11°C (0,1...19,9°F)
or
0...11°C (0,1...19,9°F)
or
or
0...40
or
or
or
Limitation of control ouputs
°C : degree centigrade
or
°F : degree Fahrenheit
or
P .U : process unit
or
dirt : direct
or
revr : reverse
or
nonE : no special function
LtCh : alarm with lock on state
hoLd : prohibition of 1st fault
or
Lt.ho : alarm with lock on state
and prohibition of 1st fault
0...99 s
0 = voltage
to.on : timer with relay on at end
or current
of count down
ouput
to.of : timer with relay open at end
or
of count down
nonE : no special function
LtCh : alarm with lock on state
hoLd : prohibition of 1st fault
Lt.ho : alarm with lock on state
prohibition of 1st fault
Cool : use as "cold" control ouput
26
J-tC : TC type J
K-tC : TC type K
t-tC : TC type T
E-tC : TC type E
b-tC : TC type B
r-tC : TC type R
S-TC : TC type S
n-tC : TC type N
Pt.dn : Pt 100 DIN
Pt.JS : Pt 100 JIS
4-20 : 4...20 mA
0-20 : 0...20 mA
0-1V : 0...1 V
0-5V : 0...5 V
1-5V : 1...5 V
0-10V : 0...10 V
no.dP : no decimal
1.dP : 1 decimal
2.dP : 2 decimals
dv.hi : alarm with high gap
dv.Lo : alarm with low gap
db.hi : high symmetrical
db.Lo : low symmetrical
FS.hi : absolute high
FS.Lo : absolute low
).